5.2.6 Eccentricity
5.2.6.1 Design eccentricity ( edi ) — It is the value of eccentricity to be used for floor i in calculations of design torsion effects.
5.2.6.2 Static eccentricity (esi) — It is the distance between centre of mass (CM) and centre of resistance (CR) of floor i.
5.2.7 Design Seismic Base Shear ( VB ) — It is the horizontal lateral force in the considered direction of earthquake shaking that the structure shall be designed for.
5.2.8 Diaphragm — It is a horizontal or nearly horizontal structural system (for example, reinforced concrete floors and horizontal bracing systems), which transmits lateral forces to vertical elements connected to it.
5.2.9 Height of Floor ( hi ) — It is the difference in vertical elevations (in metre) of the base of the building and top of floor i of the building.
5.2.10 Height of Building (h) — It is the height of building (in metre) from its base to top of roof level,
a) excluding the height of basement storeys, if basement walls are connected with the ground floor slab or basement walls are fitted between the building columns, but
b) including the height of basement storeys, if basement walls are not connected with the ground floor slab and basement walls are not fitted between the building columns.
In step-back buildings, it shall be taken as the average of heights of all steps from the base, weighted with their corresponding floor areas. And, in buildings founded on hill slopes, it shall be taken as the height of the roof from the top of the highest footing level or pile cap level.
PART 6 STRUCTURAL DESIGN — SECTION 1 LOADS, FORCES AND EFFECTS
5.2.11 Horizontal Bracing System — It is a horizontal truss system that serves the same function as a diaphragm.
5.2.12 Joints — These are portions of columns that are common to beams/braces and columns, which frame into columns.
5.2.13 Lateral Force Resisting System — It is part of the structural system, and consists of all structural members that resist lateral inertia forces induced in the building during earthquake shaking.
5.2.14 Moment-Resisting Frame — It is an assembly of beams and columns that resist induced and externally applied forces primarily by flexure.
5.2.14.1 Ordinary moment-resisting frame (OMRF)—It is a moment-resisting frame designed and detailed as per relevant good practices [6-1(7)], but not meeting special detailing requirements for ductile behaviour as per good practices [6-1(8)] or [6-1(9)], as applicable.
5.2.14.2 Special moment-resisting frame (SMRF) — It is a moment-resisting frame designed and detailed as per relevant good practices [6-1(7)], and meeting special detailing requirements for ductile behaviour as per good practices [6-1(8)] or [6-1(9)], as applicable.
5.2.15 Number of Storeys (n) — It is the number of levels of a building above the base at which mass is present in substantive amounts. This,
a) excludes the basement storeys, where basement walls are connected with the ground floor deck or fitted between the building columns; and
b) includes the basement storeys, when they are not so connected.
5.2.16 Core Structural Walls, Perimeter Columns, Outriggers and Belt Truss System — It is a structural system comprising a core of structural walls and perimeter columns, resisting the vertical and lateral loads, with
a) the core structural walls connected to select perimeter column element(s) (often termed outrigged columns) by deep beam elements, known as outriggers, at discrete locations along the height of the building; and
b) the outrigged columns connected by deep beam elements (often known as belt truss), typically at the same level as the outrigger elements.
A structure with this structural system has enhanced lateral stiffness, wherein core structural walls and perimeter columns are mobilized to act with each other
through the outriggers, and the perimeter columns themselves through the belt truss. The global lateral stiffness is sensitive to: flexural stiffness of the core element, the flexural stiffness of the outrigger element(s), the axial stiffness of the outrigged column(s), and the flexural stiffness of the outrigger elements connecting the core structural walls to the perimeter columns.
5.2.17 Principal Plan Axes — These are two mutually perpendicular horizontal directions in plan of a building along which the geometry of the building is oriented.
5.2.18 P- Δ Effect — It is the secondary effect on shear forces and bending moments of lateral force resisting elements generated under the action of the vertical loads, interacting with the lateral displacement of building resulting from seismic effects.
5.2.19 RC Structural Wall — It is a wall designed to resist lateral forces acting in its own plane.
5.2.19.1 Ordinary RC structural wall — It is a reinforced concrete (RC) structural wall designed and detailed as per good practice [6-1(10)], but not meeting special detailing requirements for ductile behaviour as per good practice [6-1(8)].
5.2.19.2 Special RC structural wall — It is a RC structural wall designed and detailed in accordance with and meeting special detailing requirements for ductile behaviour, as per good practice [6-1(8)].
5.2.20 Storey — It is the space between two adjacent floors.
5.2.20.1 Soft storey — It is one in which the lateral stiffness is less than that in the storey above. The storey lateral stiffness is the total stiffness of all seismic force resisting elements resisting lateral earthquake shaking effects in the considered direction.
5.2.20.2 Weak storey — It is one in which the storey lateral strength [cumulative design shear strength of all structural members other than that of unreinforced masonry (URM) infills] is less than that in the storey above. The storey lateral strength is the total strength of all seismic force resisting elements sharing the lateral storey shear in the considered direction.
5.2.21 Storey Drift — It is the relative displacement between the floors above and/or below the storey under consideration.
5.2.22 Storey Shear ( Vi ) — It is the sum of design lateral forces at all levels above the storey i under consideration.
5.2.23 Storey Lateral Shear Strength (Si) — It is the total lateral strength of all lateral force resisting
elements in the storey considered in a principal plan direction of the building.
5.2.24 Storey Lateral Translational Stiffness ( Ki ) — It is the total lateral translational stiffness of all lateral force resisting elements in the storey considered in a principal plan direction of the building.
5.2.25 RC Structural Wall Plan Density ( ρsw ) — It is the ratio of the cross-sectional area at the plinth level of RC structural walls resisting the lateral load and the plinth of the building, expressed as a percentage.