The minimum number of accessible changing rooms should be provided depending on the type and use of the building.
In the event that changing rooms are provided alongside a toilet area, these should comply with the specifications given in B-9.14.
A fixed bench should be set at a height of 450 mm to 480 mm above floor level. The bench should be no less than 500 mm wide, 2 000 mm in length, and be provided with a grab bar at a height of 700 mm to 800 mm with a clearance of between 50 mm and 65 mm from the wall.
A clear space of shall be beside the bench.
Coat hooks should be set at different heights, 900 mm to 1 100 mm, and additionally at least one hook at 1 400 mm.
Coat hooks, benches, locker handles and other furnishings should offer good colour and tonal contrast to their backgrounds. Non-slip floor surfaces should be used, and good lighting as well as matte finished surfaces and furnishings should be provided.
An alarm/call bell/switch may be provided (see B-9.12).
Changing rooms shall have a minimum area of .