In addition to the general requirements on fire prevention given in 3, the life safety requirements given in 4, and the fire protection requirements given in 5, the following additional requirements shall also be complied with for each type of occupancy.
For additional requirements for high rise buildings, the provisions as given in Annex E shall apply.
Atriums in building occupancies shall comply with the provisions as given in Annex F.
For fire protection requirements of commercial kitchen, cooking facilities with or without restaurants, the provisions of Annex G shall be referred.
6.1 Residential Buildings (Group A)
6.1.1 Life Safety
6.1.1.1 Subdivision
a) All locking devices, which would impede or prohibit exit, such as chain type bolts, limited opening sliding type locks and burglar locks, which are not disengaged easily by quick-releasing catches, shall be prohibited.
b) All bathroom door locks or fasteners shall be designed to permit the opening of the locked or closed door from the outside in an emergency without the use of a special key.
c) No lodging or rooming house shall have its sole means of egress pass through any non-residential occupancy in the same building.
d) Rooming and lodging houses having floor area of on any one or more floors shall have access to minimum two separate means of exits, at least one of which shall be so arranged as to have direct exit discharge.
6.1.1.2 Subdivision A-3
a) Requirements of 6.1.1.1 shall be applicable.
b) All sleeping rooms having occupancy of more than 10 persons shall have two separate and distinct exit access in different directions.
6.1.1.3 Subdivision A-4
In case of high rise apartments, of the minimum exits as specified in 4.4.2.4.3.1, the naturally ventilated exit staircases may not require the provision of fire door. However, fire door shall be provided for all other staircases and pressurized staircases.
6.1.1.4 Subdivision A-5
a) Panic bars shall be provided in the fire exits. Panic bars shall be located at a height between 865 mm and 1220 mm from the floor level.
b) All guest rooms and suites shall be protected by extended throw, quick response type sprinklers only. Also these areas shall be provided with audio-based detectors, having a sound level of at least 75 dB.
c) Horizontal-sliding doors shall not be used for door openings across corridors.
6.1.2 Additional Precautions
a) Flammable liquids for household purposes shall be kept in tightly stoppered or sealed containers. For the limits of quantities of flammable liquids to be allowed in various occupancies, reference may be made to appropriate regulations.
b) No stove or combustion heater shall be located directly under or immediately at the foot of stairs or otherwise so located as to block escape in case of malfunctioning of the stove or heater.
c) All kitchen exhaust fans, where provided, shall be fixed to an outside wall or to a duct of non-combustible material, which leads directly to the outside. The ducts shall not pass through areas having combustible materials. However, in case of centralized ducting, the duct shall be provided with adequate protection to limit the spread of fire.
d) Stores, engineering workshops, areas of high hazard, etc used for storage of substantial amount of flammable liquids shall be of 120 min fire resistance rating wall. Such areas shall be provided with fire doors, to be kept closed and shall be posted with a sign on each
side of the door in 25 mm high block letters stating—‘FIREDOOR — KEEP CLOSED’.