18.7.1 Ordinary concentrically braced frames (OCBF) should be shown to withstand inelastic deformation corresponding to a joint rotation of at least 0.02 radians without degradation in strength and stiffness below the full yield value. Ordinary concentrically braced frames meeting the requirements of this section shall be deemed to satisfy the required inelastic deformation.
18.7.1.1 Ordinary concentrically braced frames shall not be used in seismic zones IV and V and for buildings with importance factor greater than unity (I >1.0) in Seismic Zone III.
18.7.1.2 The provision in this Section apply for diagonal and X-bracing only. Specialist literature may be consulted for V and inverted V-type bracing. K-bracing shall not be permitted in systems to resist earthquake.
18.7.2 Bracing Members
18.7.2.1 The slenderness of bracing members, columns and beams shall not exceed 120.
18.7.2.2 The required compressive strength of bracing member shall not exceed 0.8 times Pd , where Pd is the design strength in axial compression (see 13.1.2)
18.7.2.3 Along any line of bracing, braces at all levels shall be provided such that for lateral loading in either direction, the tension braces will have to resist between 30 and 70 percent of the total floor shear at that level.
18.7.2.4 Bracing cross-section can be plastic, compact or semi-compact, but not slender, as defined in 9.7.2.
18.7.2.5 For all built-up braces, the spacing of tack fasteners shall be such that the unfavourable slenderness ratio of individual element, between such fasteners, shall not exceed 0.4 times the governing slenderness ratio of the brace itself. Bolted connections shall be avoided within the middle one-fourth of the clear brace length (0.25 times the length in the middle) in such built-up braces.
18.7.2.6 The bracing members shall be designed so that gross area yielding (see 12.2) and not the net area rupture (see 12.3) would govern the design tensile strength.
18.7.3 Bracing Connections
18.7.3.1 End connections in bracings shall be designed to withstand the minimum of the following:
a) A tensile force in the bracing equal to 1.2fyAg
b) Force in the brace due to load combinations in 18.2.3; and
c) Maximum force that is transferred to the brace by the system, based on analysis.
18.7.3.2 The connection should be checked for tension rupture and block shear under the load determined in 18.7.3.1.
18.7.3.3 The connection shall be designed to withstand a moment of 1.2 times the full plastic moment of the braced section about the buckling axis.
18.7.3.4 Gusset plates shall be checked for buckling out of their plane.