Table 10Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (min) of
Load Bearing
Non-load Bearing
60(3)
90(4)
120(5)
180(6)
240(7)
60(8)
90(9)
120(10)
180(11)
240(12)
i)
Reinforced cement concrete 1)
120(25) 2)
140(25) 2)
160(25) 2)
200(25) 2)
240(25) 2)
—
—
—
—
—
ii)
Unreinforced cement concrete
150
175
—
—
—
—
—
—
—
—
iii)
No-fines concrete with:a) 13 mm cement/sand or gypsum/sandb) 13 mm light weight aggregate gypsum plaster
—
—
—
—
—
150
150
150
150
150
—
—
—
—
—
150
150
150
150
150
iv)
Bricks of clay:a) Without finishb) With 13 mm lightweight aggregate gypsum plaster
9090
10090
10090
170100
170100
7575
9090
10090
17090
170100
v)
Bricks of sand lime:a) Without finishb) With 13 mm lightweight aggregate gypsum plaster
9090
10090
10090
190100
190100
7575
9090
10090
17090
170100
vi)
Blocks of concrete:a) Without finishb) With 13 mm lightweight aggregate gypsum plasterc) With 13 mm cement/sand or gypsum/sand
9090
10090
10090
—100
—100
7575
9075
10075
14090
150100
—
—
—
—
—
75
90
90
100
140
vii)
Blocks of lightweight concrete:a) Without finishb) With 13 mm lightweight aggregate gypsum plasterc) With 13 mm cement/sand or gypsum/sand
9090
10090
10090
140100
150100
7550
7563
7575
12575
14075
—
—
—
—
—
75
75
75
90
100
viii)
Blocks of aerated concrete:a) Without finishb) With 13 mm lightweight aggregate gypsum plaster
9090
10090
100100
140100
180150
50—
63—
63—
75—
100—
Walls containing at least 1 percent of vertical reinforcement.
2) Minimum thickness of actual cover to reinforcement.
Table 11Masonry Walls: Hollow (Required to Resist Fire from One Side at a Time) (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (Min) of
Load Bearing
Non-load Bearing
60(3)
90(4)
120(5)
180(6)
240(7)
30(8)
60(9)
90(10)
120(11)
180(12)
240(13)
i)
Bricks of clay:
a) Without finish
170
170
170
200
200
75
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
100
100
170
170
170
75
75
90
90
90
100
ii)
Blocks of concrete:
a) Without finish
—
—
—
—
—
90
125
125
140
140
150
b) With 13 mm cement/sand or gypsum/sand
—
—
—
—
—
90
125
125
140
140
140
c) With 13 mm lightweight aggregate gypsum plaster
190
200
200
—
—
75
90
90
100
125
125
iii)
Blocks of lightweight concrete:
a) Without finish
100
100
100
—
—
75
90
90
100
140
150
b) With 13 mm cement/sand or gypsum/sand
—
—
—
—
—
75
75
75
100
140
140
c) With 13 mm lightweight aggregate gypsum plaster
—
—
—
—
—
63
63
63
75
90
100
Table 12Framed Construction, Load Bearing (Required to Resist Fire from One Side at a Time) (Clause C-1)
Sl No.
Nature of Construction and Materials/Timber Studs at Centres not Exceeding 600 mm, Faced on Each Side with
Minimum Thickness (mm) of Protection for a Fire Resistance of 60 min
(1)
(2)
(3)
i)
Plasterboard layers with joints staggered, joints in outer layer taped and filled - Total thickness for each face
25
ii)
One layer of 12.7 mm plasterboard with a finish of lightweight aggregate gypsum plaster
13
iii)
Metal lath and plaster, thickness of plaster: a) Sanded gypsum plaster (metal lathing grade) b) Lightweight aggregate gypsum plaster
22 13
PART 4 FIRE AND LIFE SAFETY
Table 13Framed Construction, Non-Load Bearing (Required to Resist Fire from One Side at a Time) (Clause C-1)
Sl No.
Nature of Construction and Materials/Steel or Timber Frame at Centres not Exceeding 600 mm, Facings on Both Sides of
Stud Construction
Minimum Thickness (mm) of Protection for a Fire Resistance of
30 min
60 min
90 min
120 min
(1)
(2)
(3)
(4)
(5)
(6)
(7)
i) Dry lining with materials fixed direct to studs, without plaster finish:
a) One layer of plasterboard with taped and filled joints
Timber or steel
12.7
—
—
—
b) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled – Total thickness for each face
Timber or steel
19
25
—
—
c) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
Timber or steel
9
12
—
—
d) One layer of wood wool slabs
Timber
25
—
—
—
e) One layer of chipboard or of plywood
Timber or steel
18
—
—
—
ii) Lining with materials fixed direct to suds, with plaster finish:
a) Plasterboard of thickness:
1) With not less than 5 mm gypsum plaster finish
Timber or steel
9.5
—
—
—
2) With not less than 13 mm gypsum plaster finish
Timber or steel
—
12.7
—
—
iii) Wet finish:
a) Metal lath and plaster, thickness of plaster:
1) Sanded gypsum plaster
Timber or steel
13
—
—
—
2) Lightweight aggregate gypsum plaster
Timber Steel
—
13
19
25
Table 14Framed External Walls Load Bearing (Required to Resist Fire from One Side at a Time) (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of 60 min
(1)
(2)
(3)
i)
Timber studs at centres not exceeding 600 mm with internal linings of:Plasterboard layers with joints in outer layer taped and filled, total thickness of plasterboard
31
Table 15Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (A)] (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
30 min(3)
60 min(4)
90 min(5)
120 min(6)
180 min(7)
240 min(8)
i) Steel frame with an external cladding of non-combustible sheets (excluding sheet steel), with a steel supporting framework and internal lining of:
a) Metal lath and plaster, thickness of plaster:
1) Sanded gypsum plaster (metal lathing grade)
13
13
—
—
—
—
2) Lightweight aggregate gypsum plaster
10
13
15
15
15
19
b) Two layer of plasterboard with joints staggered joints in outer layer taped and filled – Total thickness
21
32
—
—
—
—
c) Plasterboard of thickness:
1) With not less than 5 mm gypsum plaster finish
12.7
—
—
—
—
—
2) With not less than 13 mm gypsum plaster finish
9.5
—
—
—
—
—
3) With not less than 10 mm lightweight aggregate gypsum plaster
9.5
—
—
—
—
—
d) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
9
9
12
12
12
12
e) One layer of wood/wool slabs without finish
—
50
—
—
—
—
f) One layer of compressed straw building slabs:
1) Without finish
50
—
—
—
—
—
2) With not less than 5 mm gypsum plaster finish
—
50
—
—
—
—
g) Aerated concrete blocks
50
50
63
63
75
100
h) Bricks of clay:
1) Without finish
75
75
90
90
100
100
2) With not less than 13 mm lightweight aggregate gypsum plaster
—
—
75
75
90
90
Table 16Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (B)] (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection to provide Sufficient Insulation to Achieve a Modified Fire Resistance of Up to 240 min
(1)
(2)
(3)
i)
Steel frame with an external cladding of sheet steel fully lapped, steel bolted and fixed to steel sheeting rails, with timber or steel supporting framework and internal lining of:
a) Metal lath and plaster, thickness of plaster:
1) Sanded gypsum plaster (metal lathing grade)
13
2) Lightweight aggregate gypsum plaster
10
b) One layer of plasterboard with joints taped and filled
12.7
c) Plasterboard of thickness with not less than 5 mm gypsum plaster finish
9.5
d) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
9
e) One layer of wood/wool slabs
25
f) One layer of compressed straw building slabs
50
g) One layer of chipboard or of plywood
18
h) Aerated concrete blocks
50
j) Bricks of clay
75
k) Any internal decorative lining with a cavity fill independently supported and retained in position of mineral fibre insulating material (excluding glass) at a density of 48 kg/m3
50
PART 4 FIRE AND LIFE SAFETY
Table 17Framed Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (C)] (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of 90 min
(1)
(2)
(3)
i) Timber frame with external cladding of weather boarding or external plywood, 9.5 mm with an internal lining of :
a) Plasterboard not less than 9.5 mm thick, finished with:
1) Gypsum plaster
13
2) Lightweight aggregate gypsum plaster
10
b) Plasterboard not less than 12.7 mm thick, finished with:
1) Gypsum plaster
10
2) Lightweight aggregate gypsum plaster
10
c) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
9
12
Table 18Reinforced Concrete Columns (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
30 min
60 min
90 min
120 min
180 min
240 min
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Fully exposed
a) Width
150
200
250
300
400
450
b) Cover
40
40
40
40
40
40
ii)
50 percent exposed
a) Width
125
160
200
200
300
350
b) Cover
40
40
40
40
40
40
iii)
One face exposed
a) Thickness
100
120
140
160
200
240
b) Cover
40
40
40
40
40
40
Table 19Concrete Beams (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
30 min(3)
60 min(4)
90 min(5)
120 min(6)
180 min(7)
240 min(8)
(1)
(2)
i)
Reinforced concrete (simply supported)
a)
Width
200
200
200
200
240
280
b)
Cover
20
20
20
40
601)
701)
ii)
Reinforced concrete (continuous)
a)
Width
200
200
200
200
240
280
b)
Cover
20
20
20
30
40
501)
iii)
Prestressed concrete (simply supported)
a)
Width
100
120
150
200
240
280
b)
Cover
25
40
551)
701)
801)
901)
iv)
Prestressed concrete (continuous)
a)
Width
80
100
120
150
200
240
b)
Cover
20
30
40
551)
701)
801)
Table 20 Concrete Floors(Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
30 min
60 min
90 min
120 min
180 min
240 min
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Reinforced concrete (simply supported)
a) Thickness
75
95
110
125
150
170
b) Cover
20
20
25
35
451)
551)
ii)
Reinforced concrete (continuous)
a) Thickness
75
95
110
125
150
170
b) Cover
20
20
20
25
35
451)
Require attention to the additional measures necessary to reduce the risk of spalling.
Table 21Concrete Floors: Ribbed Open Soffit (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
30 min(3)
60 min(4)
90 min(5)
120 min(6)
180 min(7)
240 min(8)
i)
Reinforced concrete (simply supported)
a) Thickness of floor
75
95
110
125
150
170
b) Rib width
125
125
125
125
150
175
c) Cover
20
20
35
451)
551)
651)
ii)
Reinforced concrete (continuous)
a) Thickness of floor
75
95
110
125
150
170
b) Rib width
125
125
125
125
150
175
c) Cover
20
20
20
35
451)
551)
1) Require attention to the additional measures necessary to reduce the risk of spalling.
Table 22Encased Steel Columns, 203 mm × 203 mm (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
60 min(3)
90 min(4)
120 min(5)
180 min(6)
240 min(7)
i)
Hollow protection (without an air cavity over the flanges):
a) Metal lathing with trowelled lightweight aggregate gypsum plaster 1)
13
15
20
32
—
b) Plasterboard with 1.6 mm wire binding at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified:
1) 9.5 mm plaster board
10
15
—
—
—
2) 19 mm plaster board
10
13
20
—
—
c) Asbestos insulating boards, thickness of board:
1) Single thickness of board, with 6 mm cover fillets at transverse joints
—
19
25
—
—
2) Two layers, of total thickness
—
—
—
38
50
d) Solid bricks of clay, composition or sand lime, reinforced in every horizontal joint, unplastered
50
50
50
75
100
e) Aerated concrete blocks
60
60
60
—
—
f) Solid blocks of lightweight concrete Hollow protection (with an air cavity over the flanges)
50
50
50
60
75
PART 4 FIRE AND LIFE SAFETY
Table 22(Concluded)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
ii) Asbestos insulating board screwed to 25 mm asbestos battens
12
19
—
—
—
iii) Solid protections:
a) Concrete, not leaner than 1:2:4 mix (unplastered):
1) Concrete not assumed to be load bearing, reinforced 2)
25
25
25
50
75
2) Concrete assumed to be load bearing
50
50
50
75
75
b) Lightweight concrete, not leaner than 1:2:4 mix (unplastered): concrete not assumed to be load bearing, reinforced 2)
25
25
25
40
60
1) So fixed or designed, as to allow full penetration for mechanical bond.
2) Reinforcement shall consist of steel binding wire not less than 2.3 mm in thickness, or a steel mesh weighing not less than 0.5 kg/m 2 . In concrete protection, the spacing of that reinforcement shall not exceed 200 mm in any direction.
Table 23Encased Steel Beams, 406 mm × 176 mm (Protection Applied on Three Sides) (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
30 min(3)
60 min(4)
90 min(5)
120 min(6)
180 min(7)
240 min(8)
i)
Hollow protection (without an air cavity beneath the lower flange):
a) Metal lathing with trowelled lightweight aggregate gypsum plaster 1)
13
13
15
20
25
—
b) Plasterboard with 1.6 mm wire binding 2) at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified:
1) 9.5 mm plaster board
10
10
15
—
—
—
2) 19 mm plaster board
10
10
13
20
—
—
c) Asbestos insulating boards, thickness of board :
1) Single thickness of board, with 6 mm cover fillets at transverse joints
—
—
19
25
—
—
2) Two layers, of total thickness
—
—
—
—
38
50
ii)
Hollow protection (with an air cavity below the lower flange):
a) Asbestos insulating board screwed to 25 mm asbestos battens
9
12
—
—
—
—
iii)
Solid protection :
a) Concrete, not leaner than 1:2:4 mix (unplastered):
1) Concrete not assumed to be load bearing, reinforced 3)
25
25
25
25
50
75
2) Concrete assumed to be load bearing
50
50
50
50
75
75
b) Lightweight concrete 4) , not leaner than 1:2:4 (mix) unplastered
25
25
25
25
40
60
So fixed or designed, as to allow full penetration for mechanical bond.
2) Where wire binding cannot be used, expert advice should be sought regarding alternative methods of support to enable the lower edges of the plasterboard to be fixed together and to the lower flange, and for the top edge of the plasterboard to be held in position.
Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness or a steel mesh weighing not less than 0.5kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 200mm in any direction.
Concrete not assumed to be load bearing, reinforced.
Table 24Timber Floors – Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 21 mm Finished Thickness (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection, for a Fire Resistance of
30 min
60 min
120 min
(1)
(2)
(3)
(4)
(5)
i) 37 mm (minimum) timber joists with a ceiling of:
a)
Timber lathing and plaster, plaster of thickness
15
—
—
b)
Metal lathing and plaster, thickness of plaster:
1) Sanded gypsum plaster (metal lathing grade)
15
—
—
2) Lightweight aggregate gypsum plaster
13
13
25
c)
One layer of plasterboard with taped and filled joints
12.7
—
—
d)
Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
19
31
—
e)
One layer of plasterboard not less than 9.5 mm thick, finished with:
1) Gypsum plaster
5
—
—
2) Sanded gypsum plaster
13
—
—
3) Lightweight aggregate gypsum plaster
13
—
—
f)
One layer of plasterboard not less than 12.7 mm thick, finished with:
1) Gypsum plaster
5
—
—
2) Lightweight aggregate gypsum plaster
10
—
—
g)
One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
9
12
—
Table 25Timber Floors – Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 15 mm Finished Thickness (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
30 min
60 min
120 min
(1)
(2)
(3)
(4)
(5)
i) 37 mm (minimum) timber joists with a ceiling of:
a) Timber lathing and plaster, plaster of thickness
15
—
—
b) Metal lathing and plaster, thickness of plaster for:
1) Sanded gypsum plaster (metal lathing grade)
15
—
—
2) Lightweight aggregate gypsum plaster
13
13
25
c) One layer of plasterboard with taped and filled joints
12.7
—
—
d) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
22
31
—
e) One layer of plasterboard not less than 9.5 mm thick, finish with:
1) Gypsum plaster
5
—
—
2) Sanded gypsum plaster
15
—
—
3) Lightweight aggregate gypsum plaster
13
—
—
f) One layer of plasterboard not less than 12.7 mm thick, finished with:
1) Gypsum plaster
5
—
—
2) Lightweight aggregate gypsum plaster
10
—
—
g) One layer of asbestos insulating board, with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
9
121)
—
PART 4 FIRE AND LIFE SAFETY
Table 26Timber Floors – Any Structurally Suitable Flooring of Timber or Lignocelluloses Boards (Clause C-1)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm) of Protection, for a Fire Resistance of
30 min
60 min
(1)
(2)
(3)
(4)
i) 37 mm (minimum) timber joists with a ceiling of:
a)
Timber lathing and plaster, plaster of thickness
15
—
b)
Metal lathing and plaster, thickness of plaster for :
1) Sanded gypsum plaster (metal lathing grade)
15
—
2) Lightweight aggregate gypsum plaster
13
19
c)
One layer of plasterboard with joints taped and filled and backed by timber
12.7
—
d)
Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
25
—
e)
Two layers of plasterboard, each not less than 9.5 mm thick, joints between boards staggered and outer layer finished with gypsum plaster
5
—
f)
One layer of plasterboard not less than 9.5 mm thick, finish with :
1) Sanded gypsum plaster
13
—
2) Lightweight aggregate gypsum plaster
15
—
g)
One layer of plasterboard not less than 12.7 mm thick, finished with :
1) Sanded gypsum plaster
15
—
2) Lightweight aggregate gypsum plaster
13
—
h)
One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber