a) Materials used as interior wall and ceiling and other decorative features in enclosed stations shall be non-combustible.
b) For protection against intrusion of flammable and combustible liquids and flooding of underground transit systems, any structure including emergency egress or access stairs or vent or fan shaft structure utilized for ventilation of underground system shall be permitted to be terminated at grade, provided that the level at which it is terminated is at least 450 mm above the surrounding ground level/footpath level.
c) Emergency ventilation fans, their motors, and all related components exposed to the exhaust airflow shall be designed to operate in an ambient atmosphere of 250∘ C for a minimum of 60 min.
d) Operation of the emergency ventilation system components shall be initiated from the central supervising station.
e) All types of kiosks like ticketing booth, information counter, commercial, if any, etc, shall be constructed with non-combustible materials.
f) Enclosed stations shall be provided with back-up power connected to lighting, protective signalling systems, emergency communication system, and fire command centre.
g) Emergency lighting shall be provided throughout the station as per 3.4.7.1.
h) Voice evacuation/public address system shall be provided throughout the station, and ancillary buildings as per requirements.
j) Equipment rooms shall be protected by fire suppression systems as per relevant standards.
k) Emergency command centres and emergency response procedures shall be in place.
PART 4 FIRE AND LIFE SAFETY
m) Evacuation shall take place under the guidance and control of authorized, trained system employees or other authorized personnel as warranted under an emergency situation.
n) Adequate warning signs, directional signs, exit signs shall be provided throughout the facility.
J-8 Back-up or Emergency Power Supply
The back-up/emergency power supply shall have a capacity to cater all critical loads such as emergency lighting, protective signalling system, communication system, fire station and control room, lifts providing required egress capacity, etc.
J-9 Fire Protection Facilities
The following requirements shall apply to all open and enclosed metro stations above grade. Provisions for underground stations are not covered hereunder.
J-9.1 Details of Protection and Facilities Required
J-9.1.1 Pumping Arrangements
Each station shall be provided with two pumps having a minimum discharge of 1 620 litre/min with different prime movers. It is possible to provide two electrically driven pumps, if assured back-up power is available for driving the pumps. Jockey pump having a capacity of 180 litre/min shall also be provided to take care of minor system leakages. Electrical wiring for the pumps shall be routed from outside the station buildings in any case (see also J-9.1.9).
J-9.1.2 Extinguishers
a) Water CO2 type, CO2/ABC types, shall be provided in each platform and distributed in such a way that extinguisher is available within a travel distance of 30 m from any point.
b) Water CO2 type, CO2/ABC types, shall be provided in each concourse for every 300 m² floor area and distributed in such a way that extinguisher is available within a travel distance of 30 m from any point.
c) At least one extinguisher shall be provided for each equipment room and other enclosures for every 300m2 floor area.
J-9.1.3 Small Bore Hose Reels
a) One hose reel shall be provided for every 1 000 m² floor area of station platform or part thereof subject to a travel distance of 45 m to the nearest hose reel.
b) One hose reel shall be provided for every 1000m2 floor area concourse or part thereof subject to a travel distance of 45m to the
nearest hose reel.
c) If equipment rooms are covered with hose reels for concourse and platform, it is acceptable.