(Informative)
SUGGESTED REQUIREMENTS OF FIRE PROTECTION FOR SPECIFIC INDUSTRIES (Supplementary to Table 7G)
| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) |
| i) | Artisans workshops, village and cottage industries, tiny sector industries (duly licensed by the Govt. of India) | R | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| ii) | Aggregate built-up area less than 500m2 | R | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| iii) | Aggregate built-up area from 500m2toless than 1500m2 | R | R | NR | NR | NR | NR | NR | NR | 15000 | 5000(Note 12) | R (Note 7a) |
| iv) | Aggregate built-up area from 1500m2toless than 2500m2 | R | R | NR | NR | NR | NR | NR | NR | 25000 | 5000(Note 12) | R (Note 7a) |
| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| v) | Aggregate built-up area more than2500m2 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 |
| Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) |
| vi) | Aggregate Built-up area less than 500m2 | R | R | NR | NR | NR | NR | NR | NR | 20000 | 5000(Note 12) | R (Note 7a) |
| vii) | Aggregate Built-up area from 500 m2toless than 1500m2 | R | R | NR | NR | R | NR | NR | NR | 40000 | 10000(Note 12) | R (Note 7b) |
| viii) | Aggregate Built-up area from 1500m2toless than 2500m2 | R | R | R | R | R | NR | R | R | 60000 | 15000(Note 12) | R (Note 7c) |
| ix) | Aggregate Built-up area more than2500m2 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 |
| Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) |
| x) | Aggregate built-up area less than1000 m2 | R | R | R | R | R | R | R | R | 75000 | 10000(Note 12) | R (Note 7d) |
| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| xi) | Aggregate built-up area from 1000 m2toless than 2500 m2 | R | R | R | R | R | R | R | R | 100000 | 15000(Note 12) | R (Note 7d) |
| xii) | Aggregate built-up area more than2500m2 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 |
| Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) |
| PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 |
| Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. |
| R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. |
1 The aggregate built up area of all floors of the facility could be a process building or a storage, a utility building or open storage and any other facilities as the case may be.
2a Buildings above 9 m are not permitted for factories/industries mentioned in Sl No. 1, 2 and 3 of low hazard of Annex ‘A’ Table.
2b Buildings/Plants above 18 m in height are not permitted for factories/industries mentioned in Sl No. 1 to 4 of ordinary hazard of Annex ‘A’ Table. However, where nature of process within the Plants demand heights beyond 18 m (for example, where there are tall machinery, vessels, columns, reactors, etc are involved) and occupant load is less (for example, power plants, boiler installations, etc), increase in heights can be allowed. Non-industrial occupancies within the complex but beyond operational area such as offices, residential and the like should comply with respective provisions in this NBCS according to the occupancy.
2c Buildings/plants above 15 m in height are not permitted for high hazard factories/industries. However, where there are vessels, columns, reactors, etc, are involved and specifically related to the process requirements, the heights can be more than 15 m. However, where nature of process within the building/plants demand heights beyond 15 m (for example, where there are tall machinery, vessels, columns, reactors, etc are involved) and occupant load is less (for example, power plants, boiler installations, etc), increase in heights can be allowed. Non-industrial occupancies within the complex but beyond operational area such as offices, residential and the like should comply with respective provisions in this NBCS according to the occupancy.
3 In case, the factories/industries complex consists of building(s) with occupancies having mixed hazards, fire protection systems should be governed by the highest hazard.
4 Those factories/industries which were defined or licensed as “Artisans workshops, Village and Cottage Industries, Tiny sector industries” by the Government of India should need to provide only extinguishers and buckets, their quantity and distribution should comply with IS 2190.
5 Multiple occupancy industrial estates (all in one building) should be protected according to the requirements for ‘Ordinary’ hazard industries. No high hazard occupancies should be allowed in such buildings.
6 In case of high hazard industries-A (where applicable) and high hazard industries-B like Petrochemical industries, Refineries and the like, compliance with the requirements of other agencies like Oil Industry Safety Directorate (OISD), Petroleum and Explosives Safety Organisation (PESO), Petroleum and Natural Gas Regulatory Board (PNGRB), Oil Mines Regulations (OMR), Central Electricity Authority (CEA) should be necessary in addition to those from Annex ‘A’ Table.
7a Entire occupancy should be protected by one electric driven main pump of at least 450 lpm discharge capacity at 50 m head, one standby pump of similar capacity (with reliable back-up power supply like DG Set).
7b Entire occupancy should be protected by one electric driven main pump of at least 900 lpm discharge capacity at 50 m head, one standby pump of similar capacity (with reliable back-up power supply like DG Set).
7c Entire occupancy should be protected by one electric driven main pump of at least 1 620 lpm discharge capacity at 70 m head, one standby diesel engine driven pump of similar capacity and one jockey pump of capacity of at least 180 lpm.
7d Entire occupancy should be protected by one electric driven main pump of at least 2 280 lpm discharge capacity at 70 m head, one standby diesel engine driven pump of similar capacity and one jockey pump of capacity of at least 180 lpm.
8 Entire occupancy should be protected by hydrant, sprinkler, water spray, water mist, clean agent, foam, fire alarm systems, etc as applicable in accordance with the current versions of IS 13039, IS 15105, IS 15325, IS 15519, IS 12385, IS 15693, IS 2189, IS 15908, etc in all respects that include design and installation of pumps, pipelines, etc.
9 Certain occupancies may also be protected by automatic water mist systems with appropriate (pressure) applications. Installation and design of such systems should comply to IS 15519.
10 For all occupancies, pumping capacities and water requirements should need to be provided wherever indicated in respective columns in Annex ‘N’ Table. However, where pumping capacities and water requirements are not indicated in the respective columns, reference should be made to the concerned Indian Standard codes of practices for hydrant/sprinkler/water spray, etc, for details. In either case, design and installation of systems like hydrant, sprinkler, spray systems, etc, should strictly be carried out as per provisions in respective Indian Standards stated in Note 8 above.
11 Where application of water as extinguishing medium is not appropriate due to the presence of water-reactive materials or other valid acceptable reasons, a suitable alternative extinguishing system and method should be provided in accordance with relevant Indian Standards.
12 Overhead fire water tank should be connected to hose reels and also sprinkler system (where applicable).
13 Classifications of various occupancies shown in Annex ‘B’ is only indicative for ready reference and understanding. While designing hydrant and sprinkler systems, classifications for the purpose of design and installation should strictly adhere to those available in IS 13039 and IS 15105 respectively.
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| i) | Abrasive manufacturing premises | R | R | R | NR | Required for packing material/other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| ii) | Aerated water factories, mineral water factories | R | R | R | NR | Required for packing material/ bottles and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| iii) | Agarbatti manufacturing | R | R | R | NR | Required for packing material/Finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| iv) | Analytical and/or quality control laboratories (without pilot plant) | R | R |
| Ordinary Hazard | Appendix '2' to Annex N Factories/Industries with Aggregate Built-up Area more than 2 500 m<sup>2</sup> |
|---|---|
| Sl No. Description Extinguisher Hose | Hydrant Sprinkler System Fire Alarm System Special Protection |
| Reel | System Process Blocks Storage Blocks |
| (1) (2) (3) (4) | (5) (6) (7) (8) (9) |
| propylene, poly- | 2 000 m<sup>2</sup> exceeds 2 000 m<sup>2</sup> |
| chlorotrifluroethylene, | |
| polyvinyl chloride, | |
| polyvinyl acetate, | |
| polyvinylidene | |
| chloride, vinyl chloride- | |
| vinylidene, chloride | |
| copolymer, | |
| polyvinylidene flouride, | |
| polycarbonate, | |
| phenylene oxide | |
| polymer, polysulfone, | |
| chlorinated polyether, | |
| phenolics, melamine | |
| formaldehyde, urea | |
| formaldehyde, | |
| silicones, phenol | |
| furfural, phenol | |
| formaldehyde, | |
| tetraflouro ehtylene, | |
| polyvinyl fluoride, | |
| cresol formaldehyde, | |
| ployamide (nylon). | |
| rope works, assembling | |
| of plastic goods such as | |
| toys and the like | |
| xl) Plastic goods R R | R Required if combined Raw material and Manual fire alarm system Many chemicals are |
| manufacturing | floor plate area exceeds finished goods storage for entire unit if area water reactive with water |
| polyethylene, | should be provided with of bulding(s) exceeds and alternative systems |
| Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| polypropylene, polybutylene, ethylenemethacrylic acid ionomer, polyvinyl alcohol, polyvinyl butyrate, polyvinyl formaldehyde, polystyrene, styrene-acrylonitrile copolymer, acrylonitrile- butadiene-styrene, polymethyl methacrylate, cellulose acetate, cellulose acetate butyrate, cellulose propionate, Cellulose triacetate, ethyl cellulose, acetal, epoxy, polyesters, polyurethanes, acid monomer, acrylate, allyl, methyl methacrylate, polythene | 2 000 m2 | sprinklers | 2 000 m2 | (not involving water) should be used | ||||
| xli) | Plastic goods manufacturing foamed plastics | R | R | R | R | Raw material and finished goods storage should be provided with sprinklers | Manual fire alarm system for entire unit | |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
Free Standard provided by BIS via BSB Edge Private Limited to Datta Kare - Margao(dattakare@gmail.com) 36.255.235.24.
| Appendix ‘3’ to Annex NHigh Hazard "A" Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | ||||||||
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Fire Alarm System | Special Protection | |
| Process Blocks | Storage Blocks | |||||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xxxii) | Tyre retreading and resolving factories | S | R | R | Required for all process areas where building area is more than 2 000 m2 | Required for all Raw material and finished goods godowns where the building area is more than 2 000 m2 | Automatic fire alarm systems should be provided for entire unit | |
| R – Required. NR – Not Required. S – Suitable | ||||||||
| Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N | Appendix ‘4’ to Annex N |
| High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) | High Hazard ‘B’ Factories/Industries (All Chemicals, Petroleum, Gas Processing, Petrochemicals, Fertilizer Plants, Thermal Power Plants, etc) |
| Sl No. | Description | Fire Extinguishers, Firefighting Equipment | Hydrant System, Fire Monitors, Hose Reels | Fire Alarm System | Sprinkler System | High Volume Long Range (HVLR) Monitors | Gas/HC/Fire/Heat Detection System | Automatic Heat/Fire Detection and Suppression System | Remarks |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) |
| i) | Process units (columns, boilers, furnaces, reactors, vessels, drums, etc) | R | R (Note 1) | R | R (Note 2) | Refer Note 3 | R (Note 4) | NR | |
| ii) | Tank farm areas (storage of liquid/gas flammable | R | R | R | R | R |
Free Standard provided by BIS via BSB Edge Private Limited to Datta Kare - Margao(dattakare@gmail.com) 36.255.235.24.
1 Fire water network with fire hydrants, monitors all around the process unit and tank farm areas should be provided in accordance with relevant Indian Standards, OISD. Fire hydrants should be at different platforms/levels in TPH/boilers/furnaces/columns/reactors.
2 Water sprinklers in technological platforms for all static equipment normally reflux drums, air-fin fan coolers, etc should be provided in accordance with relevant Indian Standards, OISD.
3 Elevated fire water monitors (variable flow) to fight fires at tall columns / boiler house / reactors / technological platforms, etc should be provided in accordance with relevant Indian Standards, OISD.
4 Hydrocarbon detectors, gas detectors, heat sensors at strategic / critical locations normally drain points of vessels, columns, pump drain, tank drain points, etc should be provided in accordance with relevant Indian Standards, OISD.
5 Fixed foam pourer system for Class-A products storage tanks should be provided in accordance with relevant Indian Standards, OISD.
6 Water Sprinklers ring at top and middle of tanks for water cooling in all storage tanks should be provided in accordance with relevant Indian Standards, OISD.
7 HVLR - Remote/manual operated variable flow monitors having discharge of 500 gpm to 4 000 gpm capacity should be provided as per requirement. HVLR Monitor of 10 500 gpm should be considered for large dia tanks (for > 60 M and above). Fire robot may be considered for fighting multiple tank/area fires as per the relevant Indian Standards.
8 Medium expansion foam generators (MEFG) may be provided to fight fire due to accidental spillage of flammable materials in tank dykes/spill fires.
9 Automatic site configurable linear heat detection and foam suppression system should be provided for EFR tanks (rim seal areas) Class A products.
10 Linear heat detection system, site configurable type with water mist/spray system should be provided in all conveyor belts for early detection of rise in temperature.
11 Linear heat detection system, site configurable type should be provided in all cable cellars, trenches, for early detection.
12 All electrical panels should be provided with linear heat detection and inert gas suppression system (environment friendly halon free).
13 Chlorine leakage kit, chlorine protective suit, sensors, neutraliser, etc should be provided.
14 Water mist /deluge system and nitrogen injection fire prevention system (NIFPS) with site configurable linear heat sensing detector should be provided for oil filled transformers.
15 Wireless heat and smoke detection with alarm and notification to concerned should be provided.
16 Clean agent inert gas fire suppression system (environment friendly halon free) should be provided in all control rooms.