Fire doors should comply with the following requirements:
a) Fire doors should be constructed of non-combustible material having appropriate fire resistance, and two fire doors may be fitted in an opening if each door by itself is capable of closing the opening and the two doors together achieve the required level of fire resistance.
b) All fire doors should be fitted with an automatic self-closing device, of same fire rating as the door, which is capable of closing the door from any angle and against any latch fitted to the door.
c) Any fire door fitted within an opening which is provided as a means of escape should be capable of being opened manually or by an electromagnetic or electro-mechanical device which can be activated by the presence of smoke and/or the fire alarm system, including the case of fire doors opening into pressurised exit staircases.