a) Means of Egress–public Areas — Egress from metro station should be designed to facilitate the evacuation of a pre-defined platform occupant load to a designated point of safety in pre-defined emergency scenario(s), as defined by the transit system authority.
b) Evacuation Time from Platform — Enough egress capacity should be provided to evacuate the platform occupant load within 4 min from enclosed stations and within 5.5 min from open stations.
c) Evacuation Time to Point of Safety — Further, station design should permit evacuation of the remotest person on platform to a point of safety within 6 min in case of enclosed stations and within 8 min in case of open stations.
NOTE – Evacuation time specified in (b) and (c) may be modified based on actual engineering analysis by evaluating material heat release rates, station geometry and emergency ventilation systems.
d) For open stations where the concourse is below or protected from the platform by distance or materials as determined by an appropriate engineering analysis, that concourse should be permitted to be defined as a point of safety.
e) For enclosed stations equipped with an emergency ventilation system and where the emergency ventilation system provides protection for the concourse from exposure to the effects of a train fire at the platform as confirmed by engineering analysis, that concourse is permitted to be defined as a point of safety.
H-5.2 General Arrangement
a) Means of egress from each station platform should be provided so that they are equally distributed as far as possible, in capacity and placement, throughout the length of platform.
b) There should be at least two means of egress remote from each other.
c) Means of egress may however, be allowed to converge at concourse or subsequent levels with sufficient capacity to achieve the required evacuation time.
d) As far as possible, all the egress capacity required for emergency evacuation should be provided with the unenclosed stairs and escalators which are used for normal circulation.
H-5.3 Travel Distance
The maximum travel distance on the platform to a point at which a means of egress route leaves the platform should not be more than 100 m. This should, however be subject to fulfilling the egress requirements specified in H-5.2.
H-5.4 Means of Egress
H-5.4.1 Non-public Areas
Means of egress from unoccupied non-public areas should be permitted to be merged into public means of egress.
H-5.4.2 Non-transit Occupancies
Separate means of egress should be provided for such non-transit occupancies which are segregated from the station’s public area to ensure independent evacuation from either occupancy. Such means of egress may be allowed to converge beyond station concourse area with the approval of the competent authority. Travel distance and other egress provisions of such non-transit occupancies should be in accordance with 4.4.