J-5.1 Except as described herein, points of egress and exits from the guide way should serve as emergency access routes.
J-5.2 If security fences are used along the trainway, access gates should be provided in security fences.
J-5.3 Access gates should be a minimum 1 200 mm wide and should be of the hinged or sliding type.
J-5.4 Access gates should be placed as close as practicable to the portals to permit easy access to tunnels.
J-5.5 Information that clearly identifies the route and location of each gate should be provided on the gates or adjacent thereto.
J-5.6 Access to the elevated trainway should be from stations or by mobile ladder equipment from roadways adjacent to the track way.
J-5.7 If no adjacent or crossing roadways exist for the elevated trainway, access roads at a maximum of 750 m intervals should be required.
J-5.8 Where the configuration of an open-cut trainway prevents or impedes access for firefighting, provisions should be made to permit fire fighter access to that section of trainway at intervals not exceeding 750 m.
J-5.9 All the distances mentioned in J-5.7 and J-5.8 above should be permitted with a maximum variation of percent.
J-5.10 Distance between Tunnel Hydrants
Double headed type hydrants should be provided inside tunnels.
a) The travel distance to tunnel hydrant should not be more than 30 m.
b) Tunnel hydrant should be installed on a pipe having diameter of not less than 100 mm.
J-6 Emergency Ventilation System for Trainway
J-6.1 General
J-6.1.1 The following defines the requirements for the mechanical ventilation systems used in passenger trainway area.
J-6.1.2 Mechanical emergency ventilation should be provided in underground or enclosed trainways exceeding 300 m.