J-6.3.1 The emergency ventilation system should be designed to cater the following:
a) Provide a tenable environment along the path of egress from a fire incident in enclosed station and enclosed trainways;
b) Produce sufficient airflow rates within enclosed trainways to meet critical velocity;
c) Be capable of reaching full operational mode within 180 s;
d) Address the maximum number of trains that could be between ventilation shafts during an emergency; and
e) Maintain the required airflow rates for a minimum of 2 h.
J-6.3.1.1 Where the airflow rates required to accomplish J-6.3.1 (a), J-6.3.1 (b), or approved alternative performance criteria are dependent upon the unimpaired function of the air distribution system, that system should be designed to continue operation when exposed to the conditions generated during the design incident for the duration of 2 h.
J-6.3.1.2 Where the airflow rates required to accomplish J-6.3.1(a), J-6.3.1(b), or approved alternative performance criteria are dependent upon the continued integrity of structural and architectural features, those features should be designed to remain intact when exposed to the conditions generated during the design incident for the duration determined as per J-6.3.1(e).