a) Materials used as interior wall and ceiling and other decorative features in enclosed stations should be non-combustible.
b) For protection against intrusion of flammable and combustible liquids and flooding of underground transit systems, any structure including emergency egress or access stairs or vent or fan shaft structure utilized for ventilation of underground system should be permitted to be terminated at grade, provided that the level at which it is terminated is at least 450 mm above the surrounding ground level/footpath level.
c) Emergency ventilation fans, their motors, and all related components exposed to the exhaust airflow should be rated for 250 °C for a minimum of 120 min. Emergency ventilation fans should be connected to a secondary power supply.
d) Operation of the emergency ventilation system components should be initiated from the central supervising station.
e) All types of kiosks like ticketing booth, information counter, commercial, if any, etc, should be constructed with non-combustible materials.
f) Stations should be provided with power supply as per H-8.
g) Emergency lighting should be provided throughout the station as per 3.5.6.1 and H-9.
h) Voice evacuation/public address system should be provided throughout the station, and ancillary buildings as per requirements.
j) Equipment rooms should be protected by fire suppression systems as per relevant standards.
k) Emergency command centres and emergency response procedures should be in place.
m) Evacuation should take place under the guidance and control of authorized, trained system employees or other authorized personnel as warranted under an emergency situation.
n) Adequate warning signs, directional signs, exit signs should be provided throughout the facility.
H-8 Power Supply System
H-8.1 General
The auxiliary substation at metro stations can be provided at any location, for example, ground level, concourse level, platform level, etc. The access for dismantling and replacement in future and ease of operation and maintenance of the equipment are to be ensured.
H-8.2 Uninterrupted Power Supply (UPS) System
The UPS should be an online parallel redundant system with battery backup for emergency power supply. The batteries should provide backup for a minimum 90 min. If, DG set power backup to UPS is provided, the battery backup time should be suitably selected.