Lifts counted as one of the means of egress from any level of a station should be accessed through holding areas or lobbies at that level, which should be designed as follows:
a) The holding areas or lobbies should be separated from the platform by a smoke-tight fire separation having a fire resistance rating of at least 60 min but not less than the time required to evacuate the holding area occupant load.
b) At least one stair should be accessible from the holding area.
c) The holding area should be sized to accommodate one person per 0.2 m2.
d) If the holding area includes portions of the platform, the area within 600 mm of the trainway should not be considered in the calculation;
e) Upon activation of smoke control in the platform or adjacent trainway areas, the holding area should be pressurized to a minimum of 25 Pa.
f) The holding area should be provided with emergency voice alarm devices with two-way communication to the system operations control centre.