Where escalators are equipped with the necessary controls to decelerate in a controlled manner under the full rated load, the stop should be delayed for at least 5 s before beginning deceleration, and the deceleration rate should be no greater than 0.052 m/s2.
e) Escalators with or without intermediate landings should be acceptable as a means of egress, regardless of vertical rise.
f) Escalators exposed to the outdoor environment should be provided with slip-resistant landing and floor plates.
g) Stopped escalators should be permitted to be started in the direction of egress in accordance with the requirements for stopping of escalators described in H-5.4.5(c)(3) and H-5.4.5(d).
h) Capacity and travel speed for escalators should be computed at 120 people/min and 18.5 m/min (vertical component of travel speed), respectively.
H-5.4.6 Lifts
Lifts meeting the following requirements should be counted as one of the means of egress in stations.
H-5.4.6.1 Capacity of lifts
Where lifts are counted as contributing to the means of egress capacity;
a) lifts should have a minimum of 60 min fire resistance rating;
b) they should account for no more than 50 percent of the required egress capacity;
c) at least one lift should be considered out of service, and one lift should be reserved for fire service; and
d) the capacity of each lift should be the carrying capacity of the lifts within 30 min.