Fire and Life Safety Requirements for Metro Stations
H-1 Application and Scope
The provisions of this Annex relate to the buildings constructed as part of the metro stations/metro rail systems.
H-2 Terminology — See 2.46.
H-3 General
H-3.1 Classification
Metro stations can be classified under ‘Assembly occupancies’. These include any station building or part thereof, permanent or temporary, through which people transit for the duration of time required to enter the building and board the train to depart the station platform or to alight from the train and depart from the station building.
H-3.2 Sub-classification
Metro rail system buildings can be further classified under the following headings:
a) Elevated and enclosed stations,
b) Elevated and open stations,
c) Underground (enclosed) stations, and
d) Train depots.
NOTE – The above includes all open and enclosed metro stations along with their associated ancillary structures and train depots. Elevated should mean to include ‘at-grade’ stations as well.
H-3.3 Fire Zones
Metro stations, that is, mass rapid transit, may be constructed in any Fire Zone No. 1, 2 or 3, as per the transportation requirement/policy.
H-3.4 Type of Construction
NATIONAL BUILDING CONSTRUCTION STANDARDS 2026
Metro stations should conform to Type 1 or Type 2 or combinations of Types 1 and 2 non-combustible constructions, as defined in 3.4.
H-4 Life Safety Requirements