Lifts counted as one of the means of egress should be designed as follows:
a) Shaft enclosures should be constructed as fire separations having a 120 min fire resistance rating.
b) The design should limit water flow into the shaft.
c) No more than two lifts used for means of egress or fire department access should share the same machine room or lift pit.
d) Machine rooms should be separated from each other by fire separation having a minimum fire resistance rating of 120 min.
e) The lifts should be connected to back-up power supply.
f) During emergency evacuation, the lifts should travel only between the incident level and a point of safety.
H-5.4.7 Doors and Gates
The egress capacity for doors and gates in a means of egress serving public areas should be computed as,
a) 60 people per minute (p/min) for single leaf doors and gates;
b) 0.082 people/mm-min for bi-parting multi-leaf doors and gates measured for the clear width dimension; and
c) gates in a means of egress should be designed in accordance with the requirements for doors serving as a means of egress.