a) The station control room should have the main fire alarm panel with communication system (suitable public address system) to aid floors and facilities for receiving the message from different floors.
b) Fire command centre (FCC)/station control room (SCR) should be provided with emergency lighting. All controls and monitoring of fire alarm systems, pressurization systems, smoke management systems should be done from FCC/SCR. Monitoring of integrated building management systems, CCTVs or any other critical parameters in building may also be from the FCC/SCR.
c) Details of all floor plans along with the details of firefighting equipment and installations (2 sets laminated and bound) should be maintained in fire command centre.
H-10.2.8 Fire Alarm System
An addressable fire detection and alarm system should be provided. Major components of fire alarm system should be as per IS 2189 and as specified herein :