a) Pumping Arrangements — Each station should be provided with two pumps having a minimum discharge flow rate of 2 850 litre/min with different prime movers. It is possible to provide two electrically driven pumps, if assured back-up power is available for driving the pumps. Jockey pump having a capacity of 180 litre/min should also be provided to take care of minor system leakages.
b) Flow of Hydrant Pump — For hydrant system, having three or more hydrants on any floor, the minimum flow rate for the most demanding horizontal hydrant should be 2 850 litre/min.
c) Requirement of Residual Pressure at Remotest Hydrant — Hydraulically designed hydrant system should be designed to provide the water flow rate required at a minimum residual pressure of 7 bar at the remotest located hydrant.
d) Flow of each Hydrant — A hydraulically designed hydrant system supplying three or more hydrants on any floor, hydraulic calculations and pipe sizes should be calculated by providing 946 litre/min at the three most remote hydrants and at the minimum residual pressure of 7 bar.
e) Water Requirement for Hydrant System — The minimum water supply should be capable of providing the system demand for at least 60 min.
f) Orifice plate — Required to be installed when the static pressure at the hydrant exceeds 12.1 kg/cm2.
g) Distance of Fire Hydrant (FHC) — FHC should be provided with hose box containing two lengths of hose pipes (15 m each with a nozzle). The travel distance to any hydrant should not exceed 30 m.
H-10.2.2 Manual Medium Velocity Spray Nozzle Systems
a) Design Density — A general range of water spray application rates that should apply to most ordinary combustible solids or liquids should be from 6.1 lpm/m2to 20.4 lpm/m2 of protected surface.
b) The horizontal distance between spray nozzles/open head sprinklers should not exceed 2.5 m.
c) Water Requirement for Spray System — The water supply duration for an exposure protection sprinkler system should be for a minimum of 60 min.
H-10.2.3 Water Requirement
The enclosed station should be provided with water storage of 2 00 000 litre capacity. The underground fire water storage tanks should not be more than 7 m in depth from the level having fire brigade draw-out connection, while the draw-out connection should not be more than 5 m away from tank wall. In case any of the above criteria could not be met, one additional booster pump of suitable rating should be provided to support fire brigade vehicle for proper suction of water from the tank.
H-10.2.4 Fire Extinguishers — See H-10.1.2
H-10.2.5 Inert Gas/CO2 based Fire Suppression System — See H-10.1.5
H-10.2.6 Automatic Sprinkler System — See H-10.1.7