Platforms, corridors and ramps serving as means of egress should be designed as per the following criteria:
a) A minimum clear width of 1 200 mm should be provided along all platforms, corridors, and ramps serving as means of egress
b) In computing the means of egress capacity available on platforms, corridors, and ramps, 300 mm should be deducted at each side wall and 450 mm should be deducted at platform edges that are open to the trainway.
c) The maximum means of egress capacity of platforms, corridors, and ramps should be computed at 0.0820 people/mm-min.
d) The maximum means of egress travel speed along platforms, corridors, and ramps should be computed at 38.0 m/min.
e) The means of egress travel speed for concourses and other areas where a lesser pedestrian density is anticipated should be computed at 60.0 m/min.
H-5.4.4 Stairways
a) Unenclosed stairs and escalators should be permitted to be counted as contributing to the means of egress capacity in stations.
b) Minimum widths of such unenclosed staircases should be 1 800 mm for unidirectional stairs, and 2 400 mm for bidirectional stairs.
c) Wall or floor-mounted railings on both sides should be permitted on stairs without affecting the widths stated in (b) above by more than 300 mm.
d) Enclosed stairs in the means of egress should be minimum 1 200 mm wide.
e) Capacity and travel speed for stairs should be computed at 0.0555 people/mm-min and 14.6 m/min, respectively.