a) LED lighting fixtures should be used for lighting at metro stations.
b) Emergency illumination should include illumination of means of egress, illuminated exit signs, and all other luminaires specified as necessary to provide required illumination. Emergency lighting systems should be designed and installed so that the failure of any illumination source cannot leave in total
darkness any space that requires emergency illumination. Emergency lighting should not provide less than average of 10 lux. Minimum illumination of 10 lux should be maintained on egress route.
c) Fire resistant, low smoke and zero halogen (FS) copper conductor wires should be used for wiring of emergency lighting system at underground stations. Emergency lighting system circuit should have 3 h fire survival capability at 950 °C.
d) Out of total light fixtures installed at any station, at least 30 percent of the total lights, all uniformly distributed should be connected to emergency power source, that is, UPS.
e) Emergency lighting should be powered from a source independent of that supplying the normal lighting.
H-10 Fire Protection Facilities
The following requirement should apply to all open (elevated and at-grade), and enclosed metro stations and depots.
H-10.1 The details of the protection and facilities required for open (elevated and at-grade) stations and depots are given hereunder.
H-10.1.1 Pumping Arrangements
Each station should be provided with two pumps having a minimum discharge capacity of 1 620 litre/min with different prime movers. It is possible to provide two electrically driven pumps, if assured back-up power is available for driving the pumps. Jockey pumps having a capacity of 180 litre/min should also be provided to take care of minor system leakages, (Also refer to H-10.1.9).
H-10.1.2 Fire Extinguishers
a) Water CO2 type, CO2/ABC type fire extinguisher(s) should be provided in each platform and distributed in such a way that an the extinguisher is available within a travel distance of 30 m from any point;
b) Water CO2 type, CO2/ABC type fire extinguisher(s) should be provided in each concourse for every 300 m2floor area and distributed in such a way that an extinguishers are available within a travel distance of 30 m from any point; and
c) At least one extinguisher should be provided for each equipment room and other enclosure for every 300 m2floor area.
H-10.1.3 Small Bore Hose Reels
a) One hose reel should be provided for every 1 000 m2floor area of station platform or part thereof, subject to a travel distance of 30 m to the nearest hose reel.
b) One hose reel should be provided for every 1 000 m2floor area, concourse or part thereof subject to a travel distance of 30 m to the nearest hose reel.
c) Where equipment rooms not covered by hose reel’s reach from FHCs located at concourse and platform locations, additional hose reel points should be provided to ensure its coverage.