| Table 2 Occupant Load[Clauses 4.3, 4.4.2.1 and H-4.1(j)] | Table 2 Occupant Load[Clauses 4.3, 4.4.2.1 and H-4.1(j)] | Table 2 Occupant Load[Clauses 4.3, 4.4.2.1 and H-4.1(j)] | Table 2 Occupant Load[Clauses 4.3, 4.4.2.1 and H-4.1(j)] |
| Sl No. | Building Occupancy | Net Occupant Load Factor(m2/person)(see Note 7) | Gross Occupant Load Factor(m2/person)(see Note 1) |
| (1) | (2) | (3) | (4) |
| i) | Group A: Residential | 12.5 | - |
| ii) | Group B: Educational | 3.0 | - |
| iii) | Group C: Institutional (see Note 2) | | |
| a) Nursing homes | - | 12.0 |
| b) Clinic (daycare) | - | 12.0 |
| c) Inpatient area in hospital (like ward, sleeping area) | 11.0 | - |
| d) Outpatient area in hospital | 7.0 | - |
| iv) | Group D: Assembly | | |
| a) Concentrated use without fixed seating | 0.65 | - |
| b) Less concentrated use without fixed seating such as pre-function, multipurpose hall) | 1.40 | - |
| c) Fixed seating | see Note 4 | - |
| d) Dining areas and restaurants with seating and table | 1.80 | - |
| e) Gymnasium, sports room, library and alike with equipment, stacks and the like. | 4.6 | - |
| This includes performance stages, indoor badminton court, squash court with | | |
| Table 2 (Continued) | Table 2 (Continued) | Table 2 (Continued) | Table 2 (Continued) |
| Sl No. | Building Occupancy | Net Occupant Load Factor(m2/person)(see Note 7) | Gross Occupant Load Factor(m2/person)(see Note 1) |
| (1) | (2) | (3) | (4) |
| limited number of performers and player (while audience for the same if any should be under (c) as above). | | |
| f) Swimming pool | | |
| 1) Water surface | 3.5 | - |
| 2) Deck | 2.0 | - |
| g) Mall - Basement with sales floor | 2.1 | - |
| h) Mall - Street floor | 2.1 | - |
| j) Mall - Upper sales floor | 4.3 | - |
| k) Mall - Food court | - | 1.8 |
| m) Mall - Theatre screens | - | see Note 4 |
| n) Storage/warehouse, receiving and the like | 14.3 | - |
| v) | Group F: Mercantile | | |
| a) Street floor and above | - | 2.1 |
| b) Below street floor | - | 3.0 |
| vi) | Group E: Business | 7.1 | - |
| vii) | Group E: For Datacentres | - | 20.0 |
| a) Admin areas | - | 10.0 |
| b) Data hall, server room, equipment room areas | - | 50.0 |
| | see Annex G | see Annex G |
| viii) | Group G: Industrial | - | |
| a) Low hazard | - | 20.0 |
| b) Moderate hazard | - | 15.0 |
| c) High hazard | - | 10.0 |
| ix) | Group H: Storage (see Note 5) | - | 30.0 |
| x) | Group J: Hazardous | - | 10.0 |
| NOTES | NOTES | NOTES | NOTES |
| 1 Gross area is the floor area as defined in 2.35. | 1 Gross area is the floor area as defined in 2.35. | 1 Gross area is the floor area as defined in 2.35. | 1 Gross area is the floor area as defined in 2.35. |
| 2 Occupant load factor in dormitory portions of homes for the aged, orphanages, insane asylums, etc, where sleeping | 2 Occupant load factor in dormitory portions of homes for the aged, orphanages, insane asylums, etc, where sleeping | 2 Occupant load factor in dormitory portions of homes for the aged, orphanages, insane asylums, etc, where sleeping | 2 Occupant load factor in dormitory portions of homes for the aged, orphanages, insane asylums, etc, where sleeping |
| Table 2 (Concluded) | Table 2 (Concluded) | Table 2 (Concluded) | Table 2 (Concluded) |
| SI No. | Building Occupancy | Net Occupant Load Factor (m²/person) (see Note 7) | Gross Occupant Load Factor (m²/person) (see Note 1) |
| (1) | (2) | (3) | (4) |
| accommodation is provided, should be calculated at not less than 7.5 m² gross floor area/person.3 Commercial kitchen in the above occupancies should be calculated at 9.3 m² net floor area/person.4 In case of assembly occupancy having fixed seats, the occupant load should be determined by multiplying the number of seats by 1.2.5 Car parking areas under occupancy other than storage should also be 30 m² per person.6 Usable carpet area is the total of all corridors, passages, enclosed offices/rooms excluding rack and UPS/battery foot print7 Net area is not the carpet area. See 2.36.* Gross area is highly recommended to be used than the net area, to avoid double counting. Net area is possible to be indicated for spaces having concentration of people is typical in certain occupancies; and other common spaces/areas in a floor plate may be used by the same set of occupants. Moreover, gross area provides a safer, more conservative occupant load for the entire floor, ensuring exits are sized for the maximum possible capacity. Further, net area is used for specific rooms (like classrooms or assembly halls) where the furniture and layout are predictable, but using it for an entire floor plate often underestimates the total population because it excludes corridors, closets, and wall thicknesses where people still circulate. | accommodation is provided, should be calculated at not less than 7.5 m² gross floor area/person.3 Commercial kitchen in the above occupancies should be calculated at 9.3 m² net floor area/person.4 In case of assembly occupancy having fixed seats, the occupant load should be determined by multiplying the number of seats by 1.2.5 Car parking areas under occupancy other than storage should also be 30 m² per person.6 Usable carpet area is the total of all corridors, passages, enclosed offices/rooms excluding rack and UPS/battery foot print7 Net area is not the carpet area. See 2.36.* Gross area is highly recommended to be used than the net area, to avoid double counting. Net area is possible to be indicated for spaces having concentration of people is typical in certain occupancies; and other common spaces/areas in a floor plate may be used by the same set of occupants. Moreover, gross area provides a safer, more conservative occupant load for the entire floor, ensuring exits are sized for the maximum possible capacity. Further, net area is used for specific rooms (like classrooms or assembly halls) where the furniture and layout are predictable, but using it for an entire floor plate often underestimates the total population because it excludes corridors, closets, and wall thicknesses where people still circulate. | accommodation is provided, should be calculated at not less than 7.5 m² gross floor area/person.3 Commercial kitchen in the above occupancies should be calculated at 9.3 m² net floor area/person.4 In case of assembly occupancy having fixed seats, the occupant load should be determined by multiplying the number of seats by 1.2.5 Car parking areas under occupancy other than storage should also be 30 m² per person.6 Usable carpet area is the total of all corridors, passages, enclosed offices/rooms excluding rack and UPS/battery foot print7 Net area is not the carpet area. See 2.36.* Gross area is highly recommended to be used than the net area, to avoid double counting. Net area is possible to be indicated for spaces having concentration of people is typical in certain occupancies; and other common spaces/areas in a floor plate may be used by the same set of occupants. Moreover, gross area provides a safer, more conservative occupant load for the entire floor, ensuring exits are sized for the maximum possible capacity. Further, net area is used for specific rooms (like classrooms or assembly halls) where the furniture and layout are predictable, but using it for an entire floor plate often underestimates the total population because it excludes corridors, closets, and wall thicknesses where people still circulate. |