a) Main occupant load in a transit station is the platform occupant load, on which basis the life safety provisions of transit stations are designed. Occupant loads in transit stations are mainly a function of the train carrying capacities rather than the areas of a station.
b) For calculating platform occupant loads for a multiline, multilevel or multiplatform station, maximum occupant load for each platform should be considered separately for determining the egress capacity from that platform.
c) At levels where egress routes from separate platforms converge, occupant loads of all platforms should be considered to calculate egress capacity from that level. Simultaneous loads should be considered for all egress routes passing through each level of that station.
d) Platform occupant load should be based on the greater of the AM or PM ‘peak hour loads’ generated by the system and train loads.
e) Peak hour load should be converted to peak minute loads by dividing by 60 and multiplying further by a system surge factor varying from 1.3 to 1.5, as defined by the transit system authority. Surge factor may require to be further enhanced where increased footfalls are anticipated, like stations catering to sports complex, transit oriented development, and stations serving two or more lines.
NOTE — Surge factors should be based on actual calculations by transit system authority and in no case it should be less than 1.3.
f) Platform occupant load should be determined by factoring in the peak hour entraining loads at platform edges and train loads, in emergency evacuation scenario, as defined here:
-
Train on Fire – It is assumed that a train loaded to crush capacity/link load as may be decided by the transit system authority, travelling in peak direction at peak hour has caught fire, and as per the operating procedure it is brought to the next station, whereupon it should require to be evacuated.
-
The train in this case being called the ‘incident train’ and the platform on which it is arriving being called ‘incident platform’ of the ‘incident station’.
-
Passengers waiting on all the platforms of the ‘incident station’ should require to be evacuated as well.
-
Number of passengers should be determined as defined in (g) below.
-
Only one source of fire, that is, train fire should be assumed at a time.
-
It is assumed that the train on non-incident platform should not stop at the incident station and should stop only at previous/next station.
g) Platform occupant load for emergency evacuation scenario, should be the addition of two headway entraining loads for peak direction platform, one headway entraining load for off-peak direction platforms and one crush train load/link load.
NOTE — See also H-4.1(b) and H-4.1(c)
h) Occupancy in Non-public Areas:
-
Use of designated non-public areas by station staff whose work assignments require their presence in the station structures should be permitted.
-
Unmanned plant rooms and any other areas where usual occupancy is less than 10 persons at any given time should be treated as unoccupied areas.
j) Segregation with Non-transit Occupancy:
Non-transit (and incidental) occupancies, of area up to 300 m2 (total area of all floors), should be permitted to be accommodated within the station building. Occupant load of areas under non-transit occupancies should be in accordance with Table 2
H-5 Egress Provisions