Smoke purging system, where provided in station and ancillary building, should comply with all the following requirements:
-
The smoke purging system need not be a dedicated system.
-
The purging system should have purge rate of not less than 9 air changes per hour (ACPH) or room ventilation ACPH, whichever is higher.
-
Makeup air should be drawn from adjacent area or corridor free from smoke or can be supplied by a separate mechanical system.
-
Smoke purging fans, their motors, and all related components exposed to the exhaust airflow should be fire rated and designed to operate in smoke of 250°C for a minimum of 120 min. Smoke purging fans should be connected to a secondary power supply.
-
In case of smoke/fire in entries subway, it should be rendered out of use and evacuation should be dealt procedurally.