a) The emergency ventilation system fans that are designated for use in fire and similar emergency should be capable of satisfying the emergency ventilation requirements to move train-way air in directions to provide the needed ventilation response as per engineering analysis.
b) Individual emergency ventilation fan motors should be designed to achieve their full operating speed in no more than 30 s from a stopped position when started across the line and in no more than 60 s for variable speed motors.
c) Emergency ventilation fans, their motors, and all related components exposed to the exhaust airflow should be designed to operate at 250 °C for a minimum of 2 h.
d) Local fan motor starter and related operating control device should be located away from the direct airstream of the fans to the greatest extent practical.
e) Thermal overload protective devices in fan motors, damper motors, or on motor controls used for emergency ventilation should not be permitted.
f) Non-emergency ventilation airflows that do not impact the emergency ventilation airflows should be permitted to be left operational where identified in the engineering analysis.
g) The ventilation system designated for use in emergencies should be capable of operating at full capacity in either the supply mode or exhaust mode to provide to provide the needed ventilation response where dilution of noxious products is to be maximized.
h) The ventilation system designated for use in emergencies should be capable of being turned off and dampers closed to provide the needed ventilation response where dispersion of noxious products is to be minimized.
j) Fan should be rated in accordance with the ANSI/AMCA 300, AMCA 250/ISO 13350, ASHRAE Handbook-Fundamentals, ISO 5801, and ASHRAE 149.
k) Fans that are associated only with the passengers or employee comfort and that are not designed to function as a part of emergency ventilation system should shut down automatically on identification and initiation of a fire emergency ventilation program so as not to jeopardize or conflict with emergency airflows.