The requirements should be as given below:
a) Automatic sprinklers should be installed wherever required in terms of Table 7A to Table 7J throughout the building, for uses as specified in, and in accordance with good practice [F(20)].
b) If selective sprinklering is adopted, there is a real danger of a fire starting in one of the unsprinklered area gathering momentum spreading to other areas and reaching the sprinklered areas as a fully developed fire. In such an event, the sprinklers can be rendered useless or ineffective.
c) Automatic sprinklers should be installed in false ceiling voids exceeding 800 mm in height.
d) Installation of sprinklers may be excluded in any area to be used for substation and DG set.
e) In areas having height 17 m or above such as in atria, sprinkler installations may be rendered ineffective and hence may be avoided.
f) Pressure in sprinkler system should not exceed 12 bar or else high pressure sprinkler to be installed for above 12 bar operations.
g) The maximum floor area on any one floor to be protected by sprinklers supplied by any one sprinkler system riser from an installation control valve should be based on system protection area limitations considering maximum floor area on any one floor to be 4 500 m2for all occupancies except industrial and hazardous occupancies, where Authorities should be consulted for advice based on type and nature of risk.
h) Sprinkler installation control valves, should be installed inside the fire pump room.
j) For industrial buildings, such installation control valves may be installed outside the building and Authorities should be consulted in situations where it is not possible to locate them inside the buildings. It is advisable to provide electrically operated siren for each valve outside the buildings in addition to water gongs in such case.
k) The sprinkler flow switches provided should be monitored by fire alarm panel.
It is essential to make provisions for avoiding water from sprinkler/hydrant operation entering lifts andm) electrical rooms.
n) Ramps at all levels should be protected with sprinklers.
The water based sprinkler systems are not suited for specific buildings for example, areas manufacturingp) electronic equipment, in which case alternate type of protection should only be provided.
Colour of the sprinkler piping may be matched to suit the interiors; however, in such case, the pipingq) should be provided with red colour band of about 100 mm wide, every 3 m along the length of the pipe. In no case, the sprinkler heads should be painted.
Free Standard provided by BIS via BSB Edge Private Limited to Datta Kare - Margao(dattakare@gmail.com)36.255.235.24.
r) Based on interior design or interior requirements where it is necessary to provide pendent sprinkler with no false ceiling, to achieve the sprinkler response/activation, it is required to provide about 250 mm diameter circular plate around the sprinkler.
5.1.4 Automatic High Velocity and Medium Velocity Water Spray Systems
Automatic high velocity water spray or emulsifying system should be provided for protection of outdoor and/or indoor oil-cooled transformers as applicable in accordance with good practice [F(21)] where applicable (see Annex D). Also, medium velocity water spray system should be provided for tankage (where applicable), conveyors, cable galleries and other occupancies listed in good practice [F(21)].
5.1.5 Fixed Foam Installation
Fixed foam generating system should be provided for protection of oil storage area for boilers with its ancillary storage of furnace oils in basement. Fixed foam installations can be low, medium, or high expansion types, which can be provided based on the type of fire hazards identified in the facility. High expansion foams are used for cable tunnels and other confined areas. Design and installation of foam systems should be governed by good practice [F(22)].