a) Smoke compartments should be created to ensure that in case of a fire scenario, the escape routes are not full of smoke and a safe passage is provided to firefighters to reach the fire location.
b) Smoke barriers should be provided within the ceiling at platform and concourse levels at locations and spacing as determined by the engineering analysis and should be designed to withstand temperatures up to 2 5 0 ° C for 60 min.
c) Smoke barriers should also be provided around all openings containing staircases, escalators and lifts in public areas connecting platform to levels above or below them.
d) Multiple smoke compartments catered by a combined ductwork should be provided with fire dampers for a fire barrier.
| Table 30Fire Ratings for Mass Rapid Transit Station Occupancies (Clause H-6.1) | |||||
| Sl No. | Occupancies | Fire Rating of Enclosures h Open Enclosed Station Station | Fire Rating of Doors h Open Enclosed Station Station | ||
| (1) | (2) | (3) | (4) | (5) | (6) |
| i) | Auxiliary substation, electrical UPS/battery room | 2 | 2 | 2 | 2 |
| ii) | Signalling equipment room, telecom equipment room, S&T (signalling and train control) UPS/battery room, electrical cable shafts, S&T cable shafts | 2 | 2 | 1.5 | 1.5 |
| iii) | Environmental control system (ECS) plant room, tunnel ventilation room, firemen's staircase, emergency equipment store, CDMA room, GSM room, sewage ejector room, sump pump room, chiller plant room, pump room, DG panel room | 2 | 2 | 1.5 | 1.5 |
| iv) | Station manager room, security room, stores, cleaners room, refuse storage, plumbing shafts, staff mess rooms, distribution board room and the like. | 1 | 2 | 0.5 | 1.5 |