Gas based fire extinguishing installation should be provided in accordance with good practice on premises where water or foam cannot be used for fire extinguishing because of the special nature of the contents of the buildings/areas to be protected where either the building(s) have very limited manpower or unmanned. The protection design for fixed carbon dioxide fire extinguishing system should conform to good practice [F(23)] in all respects. For some special fire risk/essential applications, carbon dioxide may not be suitable and alternate provisions should be made as per relevant standards (see 5.1.9)
NOTE — Hypoxic air technology should not be used in occupiable areas (considering the tenability aspects), and specific caution should be exercised in consultation with the Authority, regarding its applicability.
5.1.7 Firefighting equipment should be suitably located and clearly marked by luminous signs.
5.1.8 Automatic Water Mist Systems
These systems involve the use of fine water sprays for the efficient extinguishment of fires. These systems may be provided to protect areas in buildings for the uses as specified in good practice [F(24)].
5.1.9 Extinguishing Systems with Clean Agents
Alternative systems for halon gas protection systems should be provided where necessary as prescribed in this Part. These should be in accordance with the accepted standards [F(25)].