The analysis should take into consideration all the factors that affect fire safety. A report of the analysis should be submitted. If the engineering analysis is not carried out, then a mechanical ventilation system should be provided.
J-6.2 The engineering analysis of the emergency ventilation system should include the following:
a) A validated trainway analytical simulation program that provides a quantitative analysis of airflow dynamics produced in the fire scenario, a validated computational fluid dynamic (CFD) technique, or both, as approved; and
b) The no-fire (or cold) air velocities that can be measured during commissioning to confirm that a mechanical ventilation system as built meets the requirements determined by the analysis.
J-6.2.1 Where required by J-6.1.2, the mechanical ventilation system should make provision for the protection of passengers, employees, and emergency personnel from fire and smoke during a fire emergency.