a) Fare barriers complying with the following provisions should be permitted in the means of egress serving the stations. Such barriers should be designed to release, permitting unimpeded travel in the direction of egress under all the following conditions:
-
Power failure or ground fault condition;
-
Activation of the station fire alarm signal; and
-
Manual activation from a switch in a constantly attended location in the station or operations control centre.
b) Fare barriers that do not comply with the requirements of H-5.4.8(a) should be permitted in the means of egress where barriers in the equipment are designed to provide egress when a horizontal force not exceeding 66 N is applied in the egress direction.
c) Gate-type fare barriers in the means of egress should meet the following criteria:
-
Each unit should provide a minimum of 450 mm clear width at and below a height of 1 000 mm and 530 mm clear width above that height.
-
Each unit should be credited with a capacity of 50 p/min for egress calculations.
-
Fare barriers should be designed so that their failure to operate properly will not prohibit the movement of passengers in the direction of emergency egress.