One firefighting shaft should be planned for each residential building/tower, in an educational building/block, and for each compartment of institutional, assembly, business and mercantile occupancy types. In buildings/floors having three or more compartments, there should be at least two firefighting shafts to serve the compartments.
For other occupancy types, requirement of firefighting shaft should be ascertained in consultation with the local fire authority. The firefighting shaft should necessarily have connectivity directly to exit discharge or through exit passageway (having 120 min fire resistance walls) to exit discharge.
Staircase and fire lift lobby of a firefighting shaft should be smoke controlled as per 4.4.2.5 and Table 5.
It is recommended that the pressurization requirement for staircase in firefighting shaft and for other fire exit staircases in buildings greater than 60 m in height be evaluated to limit the force required to operate the door assembly (in the direction of door opening) to not more than 133 N to set the door leaf in motion. The aspect of pressurization, door area/width and door closure should be planned in consideration to the above.
D-3 Fire Safety Requirements for Lifts
The provisions as given in 7.1 to 7.2.4 under fire safety requirements of lifts in high rise buildings in Part D ‘Building Services, Section 5 Installation of Lifts, Escalators, Moving Walks and Power-Driven Parking Systems, Subsection 5A Lifts’ of this NBCS should be applicable.
D-4 Horizontal Exits and Refuge Area