H-6.1 Fire compartments should be provided in transit stations in accordance with the provisions of this section. Fire ratings of various occupancies within open stations and enclosed stations should be as indicated in Table 30.
H-6.2 Further transit station should be divided into fire compartments by means of compartment walls and compartment floors by a fire separation of at least 120 min between the following occupancies:
a) Public areas and non-public areas,
b) Transit and non-transit areas, and
c) Ancillary areas located beneath and within 3 m of the trainway in open stations.
H-6.3 No fire separation should be required for occupancies like ticketing offices, toilets, other offices and the like.
H-6.4 Incidental kiosks inside stations for other purposes like commercial use, etc should be provided with detection and a suitable automatic suppression system, if areas occupied by such occupancies exceed 10 m2.