Fire and Life Safety Requirements for Metro Trainways
J-1 Application
Provisions of this Annex should apply to all portions of underground, elevated and at-grade metro trainway including tail buffer tracks and sidings not intended to be occupied by the passengers. These provisions may be amended, if required, as per the approval of the Competent Authority.
J-2 Use and Occupancy
J-2.1 Passengers should be allowed to enter the trainway only in the case it becomes necessary to evacuate a train.
J-2.2 Passenger evacuation from train onto the trainway should take place only under the guidance and control of authorized, trained system employee or other authorized personnel as warranted under an emergency situation.
J-2.3 Warning signs in accordance with J-4.4.1 should be posted at locations where unauthorized personnel might trespass.
J-3 Construction
J-3.1 Construction Type
J-3.1.1 Cut and Cover
Where trainways are to be constructed by cut and cover method, perimeter walls, base and roof slabs and other related constructions should be of not less than Type 1 or Type 2 or combination of Types 1 and 2 non-combustible constructions as defined in this Part. The type of construction should be further determined by an engineering analysis of potential fire exposure hazards to the structure.
J-3.1.2 Bored Tunnels
Where trainway sections are to be constructed by a tunnelling method through earth, unprotected steel liners, reinforced concrete, shotcrete, or equivalent should be permitted to be used.
J-3.1.3 Rock Tunnels
Where trainway sections are to be constructed by a tunneling method through rock, steel bents with concrete liner, if lining is required, should be permitted to be used.
J-3.1.4 Underwater Tunnels
Underwater tunnels should be not less than Type 2 construction.
J-3.1.5 Mid Tunnel Ventilation Shaft and Trainway Exit structures
Mid tunnel ventilation shafts and trainway emergency egress or access stairs should not be less than Type 1 construction.
J-3.1.6 At-Grade Construction
Materials used for at-grade construction should not be less than Type 2 materials. The type of construction should be further determined by an engineering analysis of potential fire exposure hazards to the structure.
J-3.1.7 Elevated Viaduct or Portals
All elevated structures necessary for trainway support and all structures and enclosures on or under the trainway should be of not less than Type 1 or Type 2 or combination of Type 1 and Type 2 construction. The type of construction should be further determined by an engineering analysis of potential fire exposure hazards to the structure.
J-3.2 Protection against Intrusion of Flammable and Combustible Liquids and Flooding of Enclosed Trainway
Any structure including emergency egress or access stairs or vent or fan shaft structure utilized for ventilation of underground system should be permitted to be terminated at grade, provided that the level at which it is terminated is at least 450 mm above the surrounding ground level/footpath level.
J-3.3 Compartmentation
J-3.3.1 Ancillary areas should be separated from trainway areas within underwater trainway sections by construction having a minimum 180 min fire resistance rating.
J-3.3.2 Ancillary areas should be separated from trainway areas within enclosed trainway sections by construction having a minimum 120 min fire resistance rating.
J-3.4 Combustible Components
Where combustible components not specifically mentioned here are installed in a trainway, a fire hazard analysis should be conducted to determine that the level of occupant fire safety is not adversely affected by the contents.
J-3.5 Walking Surfaces
Walking surfaces designated for evacuation of passengers should be constructed of non-combustible materials.
J-4 Emergency Egress