FACP should have provision of battery for power backup in case of power failure.
The secondary power supply should have sufficient capacity to operate the system under quiescent load (system operating in a non-alarm condition) for a minimum of 24 h and, at the end of that period, should be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for 5 min.
Battery calculations should include a minimum 20 percent safety margin above the calculated required amp-hour capacity.
In case of availability of emergency generator or two reliable sources of power supply from two separate transformers, 4 h of power backup may be taken in place of 24 h.
b) Response Indicator
Generally, response indicators are provided to identify the location of detectors which are installed at unapproachable/concealed locations. Response indicator should not be provided with addressable type fire alarm system.
H-11 Station Smoke Management System
H-11.1 The subsequent clauses give the requirement of smoke extraction and smoke purging system required in enclosed metro stations. Smoke management system is not required for open (elevated and at-grade) stations.
H-11.2 Station Public Area Smoke Extraction Systems
Station public area should be provided with active smoke extraction system to maintain tenable environment for the time required for safe evacuation of passenger(s).
The smoke extraction system should be an engineered smoke control system and its design should be based on the following:
a) Fire size
The capacity of the engineered smoke extraction system should be calculated based on the incidence of a likely minimum baggage fire size of 1 MW.
b) Smoke clear height
The design smoke clear height should be above the heads of people escaping beneath it. The minimum height should be 2.0 m.
c) Perforated ceiling
For cases where the smoke reservoir is above the false ceiling, the ceiling should be of perforated type with at least 70 percent opening.
d) Makeup air
Makeup air should be drawn directly from the external space/air shaft, through inlet air ventilators or door-ways.
e) Mode of activation
1) Automatic activation
The engineered smoke extraction system should have provision of automatic activation by smoke detectors located in the fire zone. Use of smoke detectors for activation should be carefully designed, so that accidental or premature activation of smoke detectors in a non-fire zone (due to smoke spills or spread from other areas) are avoided.
2) Manual activation
A remote manual activation and control switches, as well as visual indication of the operation status of the smoke ventilation system, should also be provided at the station control room (SCR).
f) Interlocking with other systems
- Except for smoke extraction system, all other air conditioning and mechanical ventilation systems within the areas served should be shut down automatically upon activation of the smoke extraction system.
g) Standby fans/multiple fans
Either a standby fan or multiple fans with excess capacity should be provided for each mechanical smoke extraction system, such that in the event the duty fan or the largest capacity fan fails, the required smoke extraction rate will still be met. The standby fan should be automatically activated in the event the duty fan fails.
h) Emergency ventilation fans, their motors, and all related components exposed to the exhaust airflow should be rated for 250 °C for a minimum of 120 min. Emergency ventilation fans should be connected to a secondary power supply.
H-11.3 Smoke Purging System
a) For extraction of cold smoke after the extinguishing of fire, smoke purging system should be provided.
b) Smoke purging system should be provided in the following areas of underground station:
-
Station control room;
-
S and T rooms;
-
Fire pump rooms;
-
UPS rooms; and
-
Auxiliary sub-station.
For other back of house rooms, normal ventilation system may be utilized to remove the cold smoke.