a) Escalators should not account for more than one-half of the means of egress capacity at any one level.
b) In calculating the egress capacity of escalators,
-
one escalator at each level should be considered as being out of service, and
-
the escalator chosen should be the one having the most adverse effect upon egress capacity.
c) Where escalators are permitted as a means of egress in stations, the following criteria should be complied with:
-
The escalators should be constructed of non-combustible materials (exceptions like rollers and handrails should be permitted with intimation to the Competent Authority).
-
Escalators running in the direction of egress should be permitted to remain operating.
-
Escalators running in reverse to the direction of egress should be capable of being stopped either locally by a manual stopping device at the escalator or remotely by a manual stopping device at a remote location or remotely as part of a pre-planned evacuation response. A stopped escalator should be counted as equivalent to 1 m wide staircase.
d) Where provision is made for remote stopping of escalators counted as means of egress, one of the following should apply:
The stop should be delayed until it is preceded by a minimum 15 s audible signal or warning message sounded at the escalator; wherein (1) the signal or message should have a sound intensity that is at least 15 dBA above the average ambient sound level for the entire length of the escalator, (2) the signal should be distinct from the fire alarm signal, and (3) the warning message should meet audibility and intelligibility requirements.