The level of cross-passage inside the tunnel should be designed in accordance to the following requirements:
a) In trainways where passengers have to walk on the track bed during evacuation, the floor of the cross-passages in such trainways should be kept close to the level of the track bed. The maximum permitted level difference between the level of track bed and the floor of the cross-passage should be 250 mm. Further, a smooth surface for transition of level difference should be provided at such cross-passages.
b) In trainways where passengers have to walk on a walkway mounted at the level of the train floor during evacuation, the floor of the cross-passages in such trainways should be kept in level with the walkway. Further, such walkways should always be provided on the cross-passageway side of the trainway for unobstructed access to the cross-passageway.
J-4.1.7 For open-cut trainways, an engineering analysis should be conducted to evaluate the impact of the trainway configuration on safe egress from a train fire to a point of safety.
J-4.1.8 Where the engineering analysis indicates that the configuration will impact tenability beyond the immediate vicinity of the fire, egress routes should be provided such that the maximum distance from any point within the open-cut section to a point of egress from the trainway should not be more than 380 m.
J-4.1.9 All the distances mentioned in J-4.1.3, J-4.1.5 and J-4.1.8 should be permitted with a maximum variation of −0+10percent.
J-4.2 Size of Egress Routes
J-4.2.1 Cross-passageways should be a minimum of 1 200 mm in clear width and 2 100 mm in height.
J-4.2.2 The width of exit stairs should not be required to exceed 1 200 mm for enclosed trainways.
J-4.2.3 If double leaf doors wider than 1 200 mm are provided in egress routes serving trainways, then size of active leaf should not be less than 810 mm.