6.2.1 Fire Prevention
a) Buildings intended for educational occupancy should not be used for storage of any hazardous material.
b) Gymnasiums, indoor stadiums, and similar occupancies are permitted to have floors/running tracks of wood, cinder, synthetic or the like.
6.2.2 Life Safety
a) Every room with a capacity of over 45 persons in area should have at least two doorways. Exit doors should be operated by panic bars except that doors leading from classrooms directly to the outside may be equipped with the same type of lock as is used on classroom doors leading to corridor, with no provision whatsoever for locking against egress from the classroom.
b) A building, which will have only the first floor and is accessible to not more than 20 pupils at any time, may be used for school purposes with the following exceptions:
-
Exterior walls or parts of walls which are less than 900 mm from adjacent property lines should have no openings therein.
-
Classrooms may have only one exit not less than 900 mm wide.
c) Rooms or areas for use by the preschool, kindergarten, Class/Grade 1 students should be located on ground floor/level of exit discharge. Rooms or areas occupied by Class/Grade II students should be located not above one floor higher than ground floor/level of exit discharge.
d) Of the minimum exits as specified in 4.4.2.4.3.1, the naturally ventilated exit staircases, may not require provision of fire door. However, fire door should be provided for all other staircases and pressurized staircases.
6.2.3 Special Precautions
a) Storage of volatile flammable liquids should be prohibited and the handling of such liquids should be restricted to science laboratories only; and
b) All exterior openings in a boiler room or rooms containing central heating equipment, if located below an opening in another storey or if less than 3 m from other doors or windows of the same building, should be protected by a fire assembly as in 3.5.4. Such assemblies should be of fixed, automatic, or self-closing type.