J-4.3.1 Walking surfaces serving as egress routes within guide ways should have a uniform, slip-resistant design except as permitted herein:
a) Where the trainway track bed serves as the emergency egress pathway, it should be nominally level and free of obstructions.
b) Walkways that are more than 750 mm above the floor or grade below should be provided witha continuous handrail along the side opposite the trainway.
c) Raised walkways that are greater than 1 200 mm wide and located between two trainways should not be required to have a handrail.
d) Doors in the means of egress, except cross-passageway doors, should open in the direction of exit travel.
e) Doors in the means of egress should,
-
open fully when a force not exceeding 220 N is applied to the latch side of the door, and
-
be adequate to withstand positive and negative pressures caused by passing trains and the emergency ventilation system.
J-4.3.2 Horizontal sliding doors should be permitted in cross-passageways.