a) Minimum two hydrants should be provided at each platform with a hose box containing two lengths of hose pipes (15 m each with a nozzle) subject to a travel distance of 30 m to reach the nearest hydrant. Location of hydrants should be staggered for better coverage. The hydrants should cover the entire length of the platform when two hose pipes are coupled to the landing valves and used. If not fully covered, additional hydrant(s) should be provided.
Minimum two hydrants should be provided for each concourse, including commercial area, if any, with a hose box containing two lengths of hose pipes (15 m each with a nozzle), subject to a travel distance of 30 m to reach the nearest hydrant.
c) Hydrants should be provided at each entry to the station at ground and upper levels near the staircase. At least two hydrants for parking area should be provided subject to a travel distance of 30 m to the nearest hydrant.
d) In depots, fire piping should be provided along the depot boundary as ring main. The ring main should be provided with a yard hydrant every 60 m. The building should be provided with a yard hydrant, preferably at its entry, through a branch from the ring main. The inside of the building should be provided with a number of FHCs required for coverage and maintaining a maximum travel distance of 30 m to the nearest FHC. Yard hydrant in the depot should be provided as per Table 31 through branches from ring main. Other provision(s) of fire detection and suppression in the depot should be as per Table 31.
H-10.1.7 Automatic Sprinkler System
Sprinklers are required to be provided only in the commercial areas and any combustible storage area within the station (also refer H-10.1.9). Alternatively, automatic fire suppression system instead of water-based sprinkler system, as per application, is also acceptable.