a) The back-up/emergency power supply should have a capacity to cater all critical loads such as emergency lighting, protective signalling system, communication system, station control room/fire command centre, lifts providing required egress capacity, etc.
b) Power supply to these systems and equipment should be from normal and emergency (standby generator power sources with changeover facility).
c) If the power supply is taken from HT source and HT generation, the transformer should be selected with standby capacity to ensure continuity of power supply to such systems. Where parallel HV/LV supply from a separate independent source is provided with appropriate transformer for emergency, the provision of diesel generator for emergency supply may be waived off at the discretion of metro Authority. In such a scenario, in case of failure of mains power, the transfer to emergency power supply should be automatic and within 10 s for ensuring uninterrupted supply to emergency systems.