Concept of progressive evacuation in case of hospital buildings was included in detail to ensure life safety of the inmates.
-
Provisions relating to requirement of refuge area were updated including for D-6 occupancy and introduced for apartment buildings of height 60 m and above.
-
Separate provisions on atrium were included in Annex E.
-
Detailed separate provisions were included on commercial kitchens as an Annex.
-
Detailed separate provisions were included on car parking facilities in Annex G.
-
Separate provisions on fire and life safety requirements for metro stations and metro trainways were included in Annex J and Annex K, respectively.
In this revision, the publication is renamed as National Building Construction Standards (NBCS).
This NBCS (Part F) deals with safety from fire. It specifies the demarcation of fire zones, restrictions on construction of buildings in each fire zone, classification of buildings based on occupancy, types of building construction according to fire resistance of the structural and non-structural components and other restrictions and requirements necessary to minimize danger to life from fire, smoke, fumes, or panic before the buildings can be evacuated. The NBCS recognizes that safety of life is more than a matter of means of egress and accordingly deals with various matters which are considered essential to the safety of life. The NBCS therefore covers provisions relating to means of egress covering various components thereof namely exit access, exit, and exit discharge. It also covers provisions relating to fire protection of buildings through portable and fixed firefighting installations.
Fire protection techniques have to be based on the fire behaviour characteristics of different materials and structural elements of buildings. The activities pursued by the occupants of buildings must also be taken into consideration for assessing the extent of hazards, and method should then be devised by which the hazards could be minimized. An indefinite combination of variables is involved in the phenomenon of fire, all of which cannot be quantified. The requirements of this NBCS should, therefore, be taken as a guide and an engineering design approach should be adopted for ensuring a fire safe design for buildings. Depending upon the type and complexities in a building, qualified and trained fire protection engineers should be associated with the planning of buildings, so that adequate fire and life safety measures could be incorporated in the building design right from the beginning.
Absolute safety from fire is not attainable in practice. The objective of this Part is to specify measures that will provide that degree of safety from fire which can be reasonably achieved. The NBCS endeavours to avoid requirements that might involve unreasonable hardships or unnecessary inconvenience or interference with normal use and occupancy of buildings but insists upon compliance with minimum standards of fire safety necessary for building occupants and users. For ensuring compliance of fire protection equipment/installations to the laid down quality requirements, it is desirable to use such equipment/installation duly certified under the BIS, Certification Marks Scheme.
While providing guidelines for minimizing chances of occurrence of fire through passive fire protection measures, this Part does not intend to cover all aspects of general fire prevention including sources of ignition. Nor does it cover the prevention of accidental personal injuries from fire during the course of normal occupancy of buildings.
This Part while recognizing that panic in a building on fire may be uncontrollable, deals with the potential panic hazard through measures designed to prevent the development of panic. Experience indicates that panic seldom develops even in the presence of potential danger, so long as occupants of buildings are moving towards exits which they can see within a reasonable distance and with no obstruction or undue congestion in the path of travel. However, any uncertainty as to the location or adequacy of means of egress, the presence of smoke or fumes and the stoppage of travel towards the exit, such as may occur when one person stumbles and falls on stairs, may be conducive to panic. Danger from panic is greater when a large number of people are trapped in a confined area particularly when people are not adequately guided towards egress and safety notifications are not implemented or practiced. Consideration towards announcements and annunciations needs to be given to guide the occupants to safe egress routes and to control panic during situation of distress. These aspects are addressed in this Part.
Experience has shown that concealed spaces within a building, such as, space between ceiling and false ceiling, horizontal and vertical ducts, and shafts, etc, tend to act as flues/tunnels during a fire. Provisions therefore exist to provide fire stopping within such spaces.
Nothing in this Part of the NBCS should be construed to prohibit better types of building construction, more exits, or otherwise safer conditions than the minimum requirements specified in this Part.
Compliance with this Part should not be construed as eliminating or reducing the necessity for other provisions for safety of persons using a building or structure under normal occupancy conditions. Nor should any provision of this Part be construed as requiring or permitting any addition that maybe hazardous under normal occupancy conditions.
One of the major points brought out then in this Part (until NBC 2016) is the limitation of heights and areas of buildings based on fire safety of the occupants. Individual municipal corporations were free to alter the then Table 2 (of NBC 2016) based on local conditions, but the ratios of areas as maintained in the table for different occupancies and types of construction should be adhered to.
Advantage has been taken of the developments, particularly in fire resistance rating of materials, designating types of construction in a rational manner and relating the area limitations of different occupancies to different types of construction.
Halons (halogenated hydrocarbons) which exhibit exceptional firefighting and explosion prevention/ suppression characteristics have been found to possess high ozone depleting potential. They come under Group II of Annex A of the Montreal Protocol on Substances that Deplete the Ozone Layer, the international environmental agreement for phasing out ozone depleting substances. Due to increasing evidence that the ozone layer is getting depleted at a faster rate than thought earlier, the NBCS continues to take into cognizance the need to promote use of halon alternatives as fire extinguishing media.
In this revision, the following significant changes have been made:
a) Minor occupancies have been clarified, in 3.1.1.1;
b) Mixed occupancy has been detailed in 3.1.11;
c) Fire resistance rating of roofs located over 6.7 m has been updated in Table 1;
d) Occupant load factor for various occupancies has been clarified in Table 2, also with respect to the net or gross floor area;
e) Various provisions on life safety have been updated in 4;
f) Travel distance values have been updated in Table 4;
g) Compartmentation related provisions have been comprehensively updated in 4.5;
h) Fire detection and suppression systems based on the specific type and intensity of industrial hazards has been introduced under 5.4;
j) Table 7 on firefighting requirements for various occupancies has been reviewed and separately detailed (in Table 7A to Table 7J) for all the occupancies;
k) Basis for water quantity required for fire-fighting are recommended for combined system protection (using sprinkler and hose) and similarly for hose protection system in Table 7K and Table 7M, respectively;
m) Fire protection of commercial kitchen has been elaborated through reference to the detailed Indian Standard, IS 18271 : 2023 ‘Fire safety in commercial kitchen — Guidelines’;
n) Water curtain requirement for basement compartmentation has been reviewed and deleted;
p) Annex H on fire and life safety requirements for metro stations has been elaborated;
q) Annex J on fire and life safety requirements for metro trainways has been updated;
r) A new Annex M on performance based design has been introduced;
s) A new Annex N on fire protection for specific industries is included as an informative guide; and
t) Height restrictions of buildings have been eliminated.
All standards cross-referred to in the main text of this Part, are subject to revision. The parties to agreement based on this Part are encouraged to investigate the possibility of applying the most recent editions of the standards.
As the regulation of land development and buildings is a State subject and is dealt by the States and local bodies such as urban local bodies within their jurisdiction through building regulatory documents like building regulations, building byelaws, and fire regulations, this document is voluntary in nature and is non-binding. The implementation depends on adoption by concerned parties or stipulations in a contract or by appropriate adoption by the concerned authorities.
For the purpose of deciding whether a particular requirement of this Part of the NBCS is complied with, the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 : 2022 ‘Rules for rounding off numerical values (second revision)’. The number of significant places retained in the rounded off value should be the same as that of the specified value in this Part.