Available Data Regarding Fire Resistance Rating of Various Building Components
C-1 The following tables (see Table 13 to Table 29) may be used, in the absence of any validated/certified rating regarding the materials used in the structural and/or non-structural element/component.
| Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) | Table 13 Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause C-1) |
| SI No. | Nature of Construction and Materials | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of |
| SI No. | Nature of Construction and Materials | Load Bearing | Load Bearing | Load Bearing | Load Bearing | Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing |
| SI No. | Nature of Construction and Materials | 60 | 90 | 120 | 180 | 240 | 60 | 90 | 120 | 180 | 240 |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) |
| i) | Reinforced cement concrete1) | 120(25)2) | 140(25)2) | 160(25)2) | 200(25)2) | 240(25)2) | - | - | - | - | - |
| ii) | Unreinforced cement concrete | 150 | 175 | - | - | - | - | - | - | - | - |
| iii) | No-fines concrete with:a) 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 |
| b) 13 mm light weight aggregate gypsum plaster | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | |
| iv) | Bricks of clay:a) Without finish | 90 | 100 | 100 | 170 | 170 | 75 | 90 | 100 | 170 | 170 |
| b) With 13 mm light weight aggregate gypsum plaster | 90 | 90 | 90 | 100 | 100 | 75 | 90 | 90 | 90 | 100 | |
| v) | Bricks of sand lime:a) Without finish | 90 | 100 | 100 | 190 | 190 | 75 | 90 | 100 | 170 | 170 |
| b) With 13 mm light weight aggregate gypsum plaster | 90 | 90 | 90 | 100 | 100 | 75 | 90 | 90 | 90 | 100 | |
| vi) | Blocks of concrete:a) Without finish | 90 | 100 | 100 | - | - | 75 | 90 | 100 | 140 | 150 |
| Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) | Table 13 (Concluded) |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of | Minimum Thickness (mm), Excluding any Finish, for a Fire Resistance (min) of |
| Sl No. | Nature of Construction and Materials | Load Bearing | Load Bearing | Load Bearing | Load Bearing | Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing | Non-Load Bearing |
| Sl No. | Nature of Construction and Materials | 60 | 90 | 120 | 180 | 240 | 60 | 90 | 120 | 180 | 240 |
| b) With 13 mm light weight aggregate gypsum plaster | 90 | 90 | 90 | 100 | 100 | 75 | 75 | 75 | 90 | 100 | |
| c) With 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 75 | 90 | 90 | 100 | 140 | |
| vii) | Blocks of light weight concrete:a) Without finish | 90 | 100 | 100 | 140 | 150 | 75 | 75 | 75 | 125 | 140 |
| vii) | b) With 13 mm light weight aggregate gypsum plaster | 90 | 90 | 90 | 100 | 100 | 50 | 63 | 75 | 75 | 75 |
| vii) | c) With 13 mm cement/sand or gypsum/sand | - | - | - | - | - | 75 | 75 | 75 | 90 | 100 |
| viii) | Blocks of aerated concrete:a) Without finish | 90 | 100 | 100 | 140 | 180 | 50 | 63 | 63 | 75 | 100 |
| viii) | b) With 13 mm light weight aggregate gypsum plaster | 90 | 90 | 100 | 100 | 150 | - | - | - | - | - |
| 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. | 1) Walls containing at least 1 percent of vertical reinforcement.2) Minimum thickness of actual cover to reinforcement. |
| Table 14 Masonry Walls: Hollow (Required to Resist Fire from One Side at a Time) (ClauseC-1) | ||||||||||||
| Sl No. | Nature ofConstruction and Materials | Minimum Thickness (mm), Excluding any Finish,for a Fire Resistance (min)of | ||||||||||
| Load Bearing | Non-load Bearing | |||||||||||
| 60 | 90 | 120 | 180 | 240 | 30 | 60 | 90 | 120 | 180 | 240 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| I) | Bricks of clay: a) Without finish | 170 | 170 | 170 | 200 | 200 | 75 | 75 | 90 | 100 | 170 | 170 |
| Sl No. Nature ofConstruction and Materials | 60 | Minim90 | um Th Load B120 | icknes earing180 | s (mm) Resist240 | , Excl ance (30 | uding min)o60 | any Fi f Non-90 | nish,fo load Be120 | r a Fir aring180 | e240 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| (1) (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| b) With 13 mm lightweight | 170 | 170 | 170 | 200 | 200 | 75 | 75 | 90 | 100 | 170 | 170 |
| aggregate gypsum plaster | |||||||||||
| ii) Blocks of concrete: | |||||||||||
| a) Without finish | - | - | - | - | - | 90 | 125 | 125 | 140 | 140 | 150 |
| b) With 13 mm cement/sand | - | - | - | - | - | 90 | 125 | 125 | 140 | 140 | 140 |
| or gypsum/ sand | |||||||||||
| c) With 13 mm lightweight | 190 | 200 | 200 | - | - | 75 | 90 | 90 | 100 | 125 | 125 |
| aggregate gypsum plaster | |||||||||||
| iii) Blocks of lightweight | |||||||||||
| concrete: | |||||||||||
| a) Without finish | 100 | 100 | 100 | - | - | 75 | 90 | 90 | 100 | 140 | 150 |
| b) With 13 mm cement/sand | - | - | - | - | - | 75 | 75 | 75 | 100 | 140 | 140 |
| or gypsum/sand |
| Tabl | e 15 Framed Construction, Load Bearing (Required to Resi (ClauseC-1) | st Fire from One Side at a Time) |
|---|---|---|
| Sl No. | Nature of Construction andMaterials/Timber Studs at Centres not Exceeding 600 mm, Faced on Each Side with | Minimum Thickness (mm)of Protection for a Fire Resistance of 60 min |
| (1) | (2) | (3) |
| i) | Plasterboard layers with joints staggered, joints in outer layer taped and filled -Total thickness for each face | 25 |
| ii) | One layer of 12.7 mm plasterboard with a finish of lightweight aggregate gypsum plaster | 13 |
| iii) | Metal lath and plaster, thickness of plaster: a) Sanded gypsum plaster (metal lathing grade) b) Lightweight aggregate gypsum plaster | 2213 |
| Table 16 Framed Construction, Non-Load Bearing (Required to Resist Fire from One Side at a Time) (Clause C-1) | ||||||
| Sl No. | Nature of Construction and Materials/Steel or Timber Frame at Centres not Exceeding 600 mm, Facings on Both Sides of | Stud Construction | Minimum Thickness (mm) of Protection for a Fire Resistance (min) | |||
| 30 | 60 | 90 | 120 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) |
| i) | Dry lining with materials fixed direct to studs, without plaster finish | |||||
| a) One layer of plasterboard with taped and filled joints | Timber or steel | 12.7 | - | - | - | |
| b) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled - Total thickness for each face | Timber or steel | 19 | 25 | - | - | |
| c) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber | Timber or steel | 9 | 12 | - | - | |
| d) One layer of wood wool slabs | Timber | 25 | - | - | - | |
| e) One layer of chipboard or of plywood | Timber or steel | 18 | - | - | - | |
| ii) | Lining with materials fixed direct to suds, with plaster finish | |||||
| a) Plasterboard of thickness: | ||||||
| 1) With not less than 5 mm gypsum plaster finish | Timber or steel | 9.5 | - | - | - | |
| 2) With not less than 13 mm gypsum plaster finish | Timber or steel | - | 12.7 | - | - | |
| iii) | Wet finish | |||||
| a) Metal lath and plaster, thickness of plaster: | ||||||
| 1) Sanded gypsum plaster | Timber or steel | 13 | - | - | - | |
| 2) Lightweight aggregate gypsum plaster | Timber | - | 13 | 19 | 25 | |
| Steel | ||||||
| Table 17 Framed External Walls Load Bearing (Required to Resist Fire from One Side at a Time) (ClauseC-1) | ||
| SlNo. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance of 60 min |
| (1) | (2) | (3) |
| i) | Timber studs at centres not exceeding 600 mm with internal linings of: Plasterboard layers with joints in outer layer taped and filled, total thickness of plasterboard | 31 |
| Table 18 Framed External Walls Non-Load Bearing [Required to Resist Fire from Inside the Building (A)] (ClauseC-1) | |||||||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) ofProtection for a Fire Resistance (min) of | |||||
| 30 | 60 | 90 | 120 | 180 | 240 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| i) | Steel frame with an external cladding of non-combustible sheets (excluding sheet steel), with a steel supporting framework and internal lining of: | ||||||
| a) Metal lath and plaster, thickness of plaster: | |||||||
| 1) Sanded gypsum plaster (metal lathing grade) | 13 | 13 | - | - | - | - | |
| 2) Lightweight aggregate gypsum plaster | 10 | 13 | 15 | 15 | 15 | 19 | |
| b) Two layers of plasterboard with joints staggered joints in outer layer taped and filled -Total thickness | 21 | 32 | - | - | - | - | |
| c) Plasterboard of thickness: | |||||||
| 1) With not less than 5 mm gypsum plaster finish | 12.7 | - | - | - | - | - | |
| 2) With not less than 13 mm gypsum plaster finish | 9.5 | - | - | - | - | - | |
| 3) With not less than 10 mm lightweight aggregate gypsum plaster | 9.5 | - | - | - | - | - | |
| d) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating | 9 | 9 | 12 | 12 | 12 | 12 | |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) ofProtection for a Fire Resistance (min) of | |||||
| 30 | 60 | 90 | 120 | 180 | 240 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| board not less than 9 mm thick, or by timber | |||||||
| e) One layer of wood/wool slabs without finish | - | 50 | - | - | - | - | |
| f) One layer of compressed straw building slabs : | |||||||
| 1) Without finish | 50 | - | - | - | - | - | |
| 2) With not less than 5 mm gypsum plaster finish | - | 50 | - | - | - | - | |
| g) Aerated concrete blocks | 50 | 50 | 63 | 63 | 75 | 100 | |
| h) Bricks of clay: | |||||||
| 1) Without finish | 75 | 75 | 90 | 90 | 100 | 100 | |
| 2) With not less than 13 mm lightweight aggregate gypsum plaster | - | - | 75 | 75 | 90 | 90 | |
| Table 19 Framed External Walls Non-Load Bearing [(Required to Resist Fire from Inside the Building (B)] (ClauseC-1) | ||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection to Provide Sufficient Insulation to Achieve a Modified Fire Resistance of Up to 240 min |
| (1) | (2) | (3) |
| i) | Steel frame with an external cladding of sheet steel fully lapped, steel bolted and fixed to steel sheeting rails, with timber or steel supporting framework and internal lining of: | |
| a) Metal lath and plaster, thickness of plaster: | ||
| 1) Sanded gypsum plaster (metal lathing grade) | 13 | |
| 2) Lightweight aggregate gypsum plaster | 10 | |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection to Provide Sufficient Insulation to Achieve a Modified Fire Resistance of Up to 240 min |
| (1) | (2) | (3) |
| b) One layer of plasterboard with joints taped and filled | 12.7 | |
| c) Plasterboard of thickness with not less than 5 mm gypsum plaster finish | 9.5 | |
| d) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber | 9 | |
| e) One layer of wood/wool slabs | 25 | |
| f) One layer of compressed straw building slabs | 50 | |
| g) One layer of chipboard or of plywood | 18 | |
| h) Aerated concrete blocks | 50 | |
| j) Bricks of clay | 75 | |
| k) Any internal decorative lining with a cavity fill independently supported and retained in position of mineral fibre insulating material (excluding glass) at a density of 48 kg/m3 | 50 |
| Tab | le 20 Framed Walls Non-Load Bearing [Required to Resis (ClauseC-1) | t Fire from Inside the Building (C)] |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of |
| Sl No. | Protection for a Fire Resistance of | |
| Sl No. | 90 min | |
| (1)i) | (2)Timber frame with external cladding of weather boarding or external plywood, 9.5 mm with an internal lining of : | (3) |
| (1)i) | a) Plasterboard not less than 9.5 mm thick, finished with: 1) Gypsum plaster | 13 |
| (1)i) | 2) Lightweight aggregate gypsum plaster | 10 |
| (1)i) | b) Plasterboard not less than 12.7 mm thick, finished with: 1) Gypsum plaster Table 20 (Concluded) | 10 |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance of 90 min |
| (1) | (2)2) Lightweight aggregate gypsum plaster c) One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber | (3)10912 |
| Table 21 Reinforced Concrete Columns(Clause C-1) | ||||||||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||||
| 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | |
| i) | Fully exposed | a) Width | 150 | 200 | 250 | 300 | 400 | 450 |
| b) Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
| ii) | 50 percent exposed | a) Width | 125 | 160 | 200 | 200 | 300 | 350 |
| b) Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
| iii) | One face exposed | a) Thickness | 100 | 120 | 140 | 160 | 200 | 240 |
| b) Cover | 40 | 40 | 40 | 40 | 40 | 40 | ||
| Table 22 Concrete Beams(Clause C-1) | ||||||||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||||
| 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | |
| i) | Reinforced concrete (simply supported) | a) Width | 200 | 200 | 200 | 200 | 240 | 280 |
| b) Cover | 20 | 20 | 20 | 40 | 60¹⁾ | 70¹⁾ | ||
| ii) | Reinforced concrete (continuous) | a) Width | 200 | 200 | 200 | 200 | 240 | 280 |
| b) Cover | 20 | 20 | 20 | 30 | 40 | 50¹⁾ | ||
| iii) | Prestressed concrete (simply supported | a) Width | 100 | 120 | 150 | 200 | 240 | 280 |
| b) Cover | 25 | 40 | 55¹⁾ | 70¹⁾ | 80¹⁾ | 90¹⁾ | ||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||||
| 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | |
| iv) | Prestressed concrete (continuous) | a) Width | 80 | 100 | 120 | 150 | 200 | 240 |
| b) Cover | 20 | 30 | 40 | 55¹⁾ | 70¹⁾ | 80¹⁾ | ||
| ¹⁾ Require attention to the additional measures necessary to reduce the risk of spalling. | ||||||||
| Table 23 Concrete Floors (ClauseC-1) | ||||||||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||||
| 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | |
| i) | Reinforced concrete (simply supported) | a) Thickness | 75 | 95 | 110 | 125 | 150 | 170 |
| b) Cover | 20 | 20 | 25 | 35 | 451) | 551) | ||
| ii) | Reinforced concrete (continuous) | a) Thickness | 75 | 95 | 110 | 125 | 150 | 170 |
| b) Cover | 20 | 20 | 20 | 25 | 35 | 451) | ||
| 1) Require attention to the additional measures necessary to reduce the risk of spalling. | ||||||||
| Table 24 Concrete Floors: Ribbed Open Soffit (ClauseC-1) | ||||||||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||||
| 30 | 60 | 90 | 120 | 180 | 240 | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | |
| i) | Reinforced concrete (simply supported) | a) Thickness of floor | 75 | 95 | 110 | 125 | 150 | 170 |
| b) Rib width | 125 | 125 | 125 | 125 | 150 | 175 | ||
| c) Cover | 20 | 20 | 35 | 451) | 551) | 651) | ||
| ii) | Reinforced concrete (continuous) | a) Thickness | 75 | 95 | 110 | 125 | 150 | 170 |
| b) Width | 125 | 125 | 125 | 125 | 150 | 175 | ||
| c) Cover | 20 | 20 | 20 | 35 | 451) | 551) | ||
| 1) Require attention to the additional measures necessary to reduce the risk of spalling. | ||||||||
| Table 25 Encased Steel Columns, 203 mm × 203 mm(Clause 3.4.3 and C-1) | ||||||
| Sl No. | Nature of Construction and Materials | Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance (min) of | ||||
| 60 | 90 | 120 | 180 | 240 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) |
| i) | Hollow protection (without an air cavity over the flanges): | |||||
| a) Metal lathing with trowelled lightweight aggregate gypsum plaster¹⁾ | 13 | 15 | 20 | 32 | - | |
| b) Plasterboard with 1.6 mm wire binding at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified: | ||||||
| 1) 9.5 mm plaster board | 10 | 15 | - | - | - | |
| 2) 19 mm plaster board | 10 | 13 | 20 | - | - | |
| c) Asbestos insulating boards, thickness of board: | ||||||
| 1) Single thickness of board, with 6 mm cover fillets at transverse joints | - | 19 | 25 | - | - | |
| 2) Two layers of total thickness | - | - | - | 38 | 50 | |
| d) Solid bricks of clay, composition, or sand lime, reinforced in every horizontal joint, ulastered | 50 | 50 | 50 | 75 | 100 | |
| e) Aerated concrete blocks | 60 | 60 | 60 | - | - | |
| f) Solid blocks of lightweight concrete Hollow protection (with an air cavity over the flanges) | 50 | 50 | 50 | 60 | 75 | |
| ii) | Asbestos insulating board screwed to 25 mm asbestos battens | 12 | 19 | - | - | - |
| iii) | Solid protections | |||||
| a) Concrete, not leaner than 1:2:4 mix (unplastered): | ||||||
| 1) Concrete not assumed to be load bearing, reinforced²⁾ | 25 | 25 | 25 | 50 | 75 | |
| 2) Concrete assumed to be load bearing | ||||||
| Table 26 Encased Steel Beams, 406 mm × 176 mm (Protection Applied on Three Sides) (Clause3.4.3andC-1) | |||||||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min) of | |||||
| 30 | 60 | 90 | 120 | 180 | 240 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| i) | Hollow protection (without an air cavity beneath the lower flange): | ||||||
| a) Metal lathing with trowelled lightweight aggregate gypsum plaster1) | 13 | 13 | 15 | 20 | 25 | - | |
| b) Plasterboard with 1.6 mm wire binding2) at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified: | |||||||
| 1) 9.5 mm plaster board | 10 | 10 | 15 | - | - | - | |
| 2) 19 mm plaster board | 10 | 10 | 13 | 20 | - | - | |
| c) Asbestos insulating boards, thickness of board : | |||||||
| 1) Single thickness of board, with 6 mm cover | - | - | 19 | 25 | - | - | |
| 2) Two layers of total thickness | - | - | - | - | 38 | 50 | |
| ii) | Hollow protection (with an air cavity below the lower flange): | ||||||
| a) Asbestos insulating board screwed to 25 mm asbestos battens | 9 | 12 | - | - | - | - | |
| iii) | Solid protection : | ||||||
| a) Concrete, not leaner than 1 : 2 : 4 mix (unplastered): | 25 | 25 | 25 | 25 | 50 | 75 | |
| 1) Concrete not assumed to be load bearing, reinforced3) | 50 | 50 | 50 | 50 | 75 | 75 | |
| 2) Concrete assumed to be load bearing | |||||||
| b) Lightweight concrete), not leaner than 1: 2: 4 (mix) unplastered | |||||||
| Table 27 Timber Floors - Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 21 mm Finished Thickness (ClauseC-1) | ||||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min)of | ||
| 30 | 60 | 120 | ||
| (1) | (2) | (3) | (4) | (5) |
| i) | 37 mm (minimum) timber joists with a ceiling of: | |||
| a) Timber lathing and plaster, plaster of thickness | 15 | - | - | |
| b) Metal lathing and plaster, thickness of plaster: | ||||
| 1) Sanded gypsum plaster (metal lathing grade) | 15 | - | - | |
| 2) Lightweight aggregate gypsum plaster | 13 | 13 | 25 | |
| c) One layer of plasterboard with taped and filled joints | 12.7 | - | - | |
| d) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 19 | 31 | - | |
| e) One layer of plasterboard not less than 9.5 mm thick, finished with: | ||||
| 1) Gypsum plaster | 5 | - | - | |
| 2) Sanded gypsum plaster | 13 | - | - | |
| 3) Lightweight aggregate gypsum plaster | 13 | - | - | |
| f) One layer of plasterboard not less than 12.7 mm thick, finished with: | ||||
| 1) Gypsum plaster | 5 | - | - | |
| 2) Lightweight aggregate gypsum plaster | 10 | - | - | |
| g) One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 9 | 12 | - | |
| Table 28 Timber Floors — Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 15 mm Finished Thickness(Clause C-1) | ||||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min) of | ||
| 30 | 60 | 120 | ||
| (1) | (2) | (3) | (4) | (5) |
| i) | 37 mm (minimum) timber joists with a ceiling of: | |||
| a) Timber lathing and plaster, plaster of thickness | 15 | - | - | |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min) of | ||
| 30 | 60 | 120 | ||
| (1) | (2) | (3) | (4) | (5) |
| b) Metal lathing and plaster, thickness of plaster for: | ||||
| 1) Sanded gypsum plaster (metal lathing grade) | 15 | - | - | |
| 2) Lightweight aggregate gypsum plaster | 13 | 13 | 25 | |
| c) One layer of plasterboard with taped and filled joints | 12.7 | - | - | |
| d) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 22 | 31 | - | |
| e) One layer of plasterboard not less than 9.5 mm thick, finish with: | ||||
| 1) Gypsum plaster | 5 | - | - | |
| 2) Sanded gypsum plaster | 15 | - | - | |
| 3) Lightweight aggregate gypsum plaster | 13 | - | - | |
| f) One layer of plasterboard not less than 12.7 mm thick, finished with: | ||||
| 1) Gypsum plaster | 5 | - | - | |
| 2) Lightweight aggregate gypsum plaster | 10 | - | - | |
| g) One layer of asbestos insulating board, with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 9 | 12 1) | - | |
| 1) Finished on top with 25 mm minimum thick glass fibre or mineral wool laid between joints. | ||||
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min) of | |
| 30 | 60 | ||
| (1) | (2) | (3) | (4) |
| i) | 37 mm (minimum) timber joists with a ceiling of: | ||
| a) Timber lathing and plaster, plaster of thickness | 15 | - | |
| Sl No. | Nature of Construction and Materials | Minimum Thickness (mm) of Protection for a Fire Resistance (min) of | |
| 30 | 60 | ||
| (1) | (2) | (3) | (4) |
| b) Metal lathing and plaster, thickness of plaster for : | |||
| 1) Sanded gypsum plaster (metal lathing grade) | 15 | - | |
| 2) Lightweight aggregate gypsum plaster | 13 | 19 | |
| c) One layer of plasterboard with joints taped and filled and backed by timber | 12.7 | - | |
| d) Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness | 25 | - | |
| e) Two layers of plasterboard, each not less than 9.5 mm thick, joints between boards staggered and outer layer finished with gypsum plaster | 5 | - | |
| f) One layer of plasterboard not less than 9.5 mm thick, finish with : | |||
| 1) Sanded gypsum plaster | 13 | - | |
| 2) Lightweight aggregate gypsum plaster | 15 | - | |
| g) One layer of plasterboard not less than 12.7 mm thick, finished with : | |||
| 1) Sanded gypsum plaster | 15 | - | |
| 2) Lightweight aggregate gypsum plaster | 13 | - | |
| h) One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber | 12 | - | |