a) Fire detection system should be of the addressable type. Detectors are required to be provided only in areas where there is false ceiling(s)/ false floor(s) and areas for equipment rooms. Wherever there are false ceilings/false floors with perforation less than 70 percent, the detectors should be provided both above and below false ceiling/false floor, giving due consideration to the depth of false ceiling/flooring. In open stations, in areas having high heights and cross-ventilation, detectors will not be effective and hence it can be dispensed. Detector(s) should be provided in lift shaft(s) and escalator pit(s) also.
b) Spacing of detectors and devices should be as per [4(26)].
c) Manual call stations(s) should be provided at central location(s) on each platform (near emergency stop plunger) and at least two on the concourse, on each sidewall. When the concourse is in two halves, at least one manual call station should be provided on each side.
H-10.1.5 Inert Gas/CO2/ based fire Suppression System
AIS HT, Main LT and panel supplying power to UPS, DG change-over, fire pump panel and transformers at the stations should be protected with the inert gas/ CO2 based fire suppression system in accordance with IS 15506/ IS 15525/IS 15501/IS 15528. A suitable detection mechanism should be provided for triggering the suppression system automatically.