a) Fire resistant/survival, low smoke zero halogen, copper conductor, armoured, cross linked polyethylene (XLPE) insulated cables should be used at enclosed stations for fire and life safety equipment like fire alarm system (FAS), tunnel ventilation fans, smoke extraction fans, staircase pressurization fans, fire pumps, emergency lighting, etc.
b) All cables and wiring used for fire and life safety equipment should have a 3 h fire survival capability at 950 °C.
c) For all other essential services at enclosed stations like chillers, AHU, normal lighting, chilled water pumps etc. flame retardant, low smoke zero-halogen (LSZH), armoured, XLPE insulated aluminium/copper conductor cables should be used.
d) At open stations, flame retardant, low smoke halogen free (FRLSH), armoured, XLPE insulated aluminium/copper conductor cables should be used for power supply.