A tenable environment should be maintained in the path of egress. The tenability criteria considerations are given hereunder:
a) Smoke obstruction:
-
Internally illuminated signage (80 lux) discernible at 30 m.
-
Walls and doors or externally illuminated signage discernible at 10 m.
b) Heat effects:
-
Exposure temperature (occupied zone) ≤ 6 0 ° C for 10 min.
-
Radiant heat exposure ≤ 2.5 kW/m2
c) Carbon monoxide – The smoke extraction system to be designed to maintain fractional effective dose (FED) of less than 0.3. The permissible exposure to carbon monoxide should be as per following table:
| Sl No. | Time min | Maximum Carbon Monoxide Exposure ppm |
|---|---|---|
| (1) | (2) | (3) |
| i) | 4 | 1 706 |
| ii) | 6 | 1 138 |
| iii) | 10 | 683 |
| iv) | 15 | 455 |
| v) | 30 | 228 |
| vi) | 60 | 114 |
| vii) | 240 | 28 |
d) Velocity – Air velocity should be greater than or equal to 0.75 m/s and less than or equal to 11 m/s along the path of egress.
e) Noise – Noise level along the path of egress should not exceed 85 dBA at any point 1.5 m above walking surface.