| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) | Minimum FirefightingRequirements for Factories/Industries -LOWHAZARD (Notes 1, 2a, 3, 4, 5 and 13) |
| i) | Artisans workshops, village and cottage industries, tiny sector industries (duly licensed by the Govt. of India) | R | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| ii) | Aggregate built-up area less than 500m2 | R | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| iii) | Aggregate built-up area from 500m2toless than 1500m2 | R | R | NR | NR | NR | NR | NR | NR | 15000 | 5000(Note 12) | R (Note 7a) |
| iv) | Aggregate built-up area from 1500m2toless than 2500m2 | R | R | NR | NR | NR | NR | NR | NR | 25000 | 5000(Note 12) | R (Note 7a) |
| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| v) | Aggregate built-up area more than2500m2 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 | Pl. see Appendix"1" and also Notes 8, 9, 10 and 11 |
| Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) | Minimum Firefighting requirements for Factories/Industries -ORDINARY HAZARD (Notes 1, 2b, 3, 5 and 13) |
| vi) | Aggregate Built-up area less than 500m2 | R | R | NR | NR | NR | NR | NR | NR | 20000 | 5000(Note 12) | R (Note 7a) |
| vii) | Aggregate Built-up area from 500 m2toless than 1500m2 | R | R | NR | NR | R | NR | NR | NR | 40000 | 10000(Note 12) | R (Note 7b) |
| viii) | Aggregate Built-up area from 1500m2toless than 2500m2 | R | R | R | R | R | NR | R | R | 60000 | 15000(Note 12) | R (Note 7c) |
| ix) | Aggregate Built-up area more than2500m2 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 | Pl. see Appendix "2" and also Notes 8, 9, 10 and 11 |
| Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) | Minimum Firefightingrequirements for Factories/Industries -High Hazard 'A' (Notes 2c, 5 and 13) |
| x) | Aggregate built-up area less than1000 m2 | R | R | R | R | R | R | R | R | 75000 | 10000(Note 12) | R (Note 7d) |
| Sl No. | Type of Factory | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Type of Installation | Recommended Water Supply litre | Recommended Water Supply litre | Recommended Pump Capacity litre per minute |
| Sl No. | Type of Factory | Extinguisher | Small Bore Hose Reels | Wet Riser | Down Comer | Yard Hydrant | Automatic Sprinkler System | Manual Fire Alarm System | Automatic Fire Detection & Alarm System | Static Tank at Ground Level | Overhead / Terrace Tank | Fire Pump Ground Level |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| xi) | Aggregate built-up area from 1000 m2toless than 2500 m2 | R | R | R | R | R | R | R | R | 100000 | 15000(Note 12) | R (Note 7d) |
| xii) | Aggregate built-up area more than2500m2 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 | Pl. seeAppendix '3' and also Notes 8, 9, 10 and 11 |
| Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) | Minimum Firefightingrequirements for Factories/Industries -High Hazard "B" (Notes 2c and 6) |
| PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 | PleaseseeAppendix '4' and also Notes 8, 9, 10 and 11 |
| Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. | Firefighting provisions shouldcomply with various provisions contained in Note 8. In addition, all factories/industries shouldbe protected as per the applicable standards like oil industry safety directorate (OISD) or others as specified in Note 6. |
| R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. | R -Required. NR -Not Required. |