3.1.11.1 These include any building having multiple occupancy where the occupancies are intermingled. The following table guides on the possible mixing of occupancies (two or more occupancies may be mixed) in a building.
| Sl No. | Occupancy to be Mixed with | Minimum Required Fire Resistance Rating for the Separation between Any Two Occupancies in min | ||||||||||
| Residential | Educational | Institutional | Assembly | Business | Mercantile | Industrial | Storage | Hazardous | ||||
| Low (G-1) | Moderate (G-2) | High (G-3) | ||||||||||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) |
| i) | Residential | - | 120 | 120 | 120 | 120 | 120 | 120 | NP | NP | NP | NP |
| ii) | Educational | 120 | - | 120 | 120 | 120 | 120 | NP | NP | NP | NP | NP |
| iii) | Institutional | 120 | 120 | - | 120 | 120 | 120 | NP | NP | NP | NP | NP |
| iv) | Assembly | 120 | 120 | 120 | - | 120 | 120 | 120 | 120 | NP | NP | NP |
| v) | Business | 120 | 120 | 120 | 120 | - | 120 | 120 | 120 | 240 | NP | NP |
| vi) | Mercantile | 120 | 120 | 120 | 120 | 120 | - | 120 | 120 | NP | 120 | NP |
| vii) | Industrial - Low (G-1) | 120 | NP | NP | 120 | 120 | 120 | - | 120 | 240 | 120 | NP |
| viii) | Industrial - Moderate (G-2) | NP | NP | NP | 120 | 120 | 120 | 120 | - | 240 | 180 | 240 |
| ix) | Industrial - High (G-3) | NP | NP | NP | NP | 240 | NP | 240 | 240 | - | 240 | 240 |
| x) | Storage | NP | NP | NP | NP | NP | 120 | 120 | 180 | 240 | - | 240 |
| xi) | Hazardous | NP | NP | NP | NP | NP | NP | NP | 240 | 240 | 240 | - |
| NP - Not permitted, being highly dangerous/vulnerable. | ||||||||||||
3.1.11.2 For mixed occupancy building typology as above, if these co-exist in a building (such as large retail occupancy and business occupancy), in so far as fire protection is concerned, the entire building should be governed by the most restrictive provisions of this NBCS among those applicable for individual occupancies. However, the exits can be shared between mixed occupancies provided its aggregate provision meets the requirement of the mixed occupancy, and should be permitted if such exits are with unrestricted egress of the occupants based on the business operational hours of the occupancies sharing such exits. If such unrestricted egress of the mixed-use occupancy is not planned, each occupancy should be provided with its independent exits.
Exits in such mixed occupancy should be so arranged as to ensure that means of egress is not decreased in the direction of egress travel.
Further, in such mixed occupancies, the occupancies are also required to be separated (horizontally and/or vertically as the case may be) by fire resistance rating, see 3.1.11.1.
3.1.12 Where change in the occupancy of any building places it in a different group or in a different subdivision of the same group, such building should be made to comply with the requirements of this NBCS for the new group or its subdivision.
3.1.13 Where the new occupancy of a building is less hazardous, based on life and fire risk, than its existing occupancy, it should not be necessary to conform to the requirements of this NBCS for the new group or its subdivision.
3.1.14 A certificate of occupancy should be necessary, before any change is effected in the character of occupancy of any building.
3.2.1 Temporary buildings and structures may be permitted according to the purpose for which these are to be used, by special permit from the Authority for a limited period and subject to such conditions as may be imposed in the permit.
3.2.2 Such buildings and temporary structures should be completely removed on the expiry of the period specified in the permit.
3.2.3 Adequate fire precautionary measures in the construction of temporary structures and Pandals should be taken in accordance with good practice [F(4)].
The existing buildings need not be required to comply with the requirements of this part unless these are altered, or in the opinion of the Local Authority, such building constitutes a hazard to the safety of the adjacent property or to the occupants of the building itself or is an unsafe building. In the event of alteration, it should be necessary to obtain permission of the Authority for such alteration consistent with fire hazard.
Alterations/modifications/renovations should be accomplished so as to ensure conformity with all the safety requirements of the new buildings. Such alterations should not in any way bring down level of fire and life safety below that which existed earlier. Any addition or alterations or construction of cubicles or partitioning (that will effect/increase the travel distance requirement), changes in the typology of the occupancy or densification of an existing occupancy for floor area exceeding 1 000 m should be with the approval of local fire authority.
All buildings should satisfy certain requirements, which contribute, individually and collectively, to the safety of life from fire, smoke, fumes, and panic arising from these or similar causes. There are, however, certain general principles and common requirements, which are applicable to all or most of the occupancies.
Table 1 Fire Resistance Ratings of Structural and Non-Structural Elements (in minutes)
(Clauses 3.4.1, 3.4.2, 3.5.9.1, 3.5.9.2 and F-2.1)
| Sl No. | Structural/Non-Structural Element | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction |
| Sl No. | Structural/Non-Structural Element | Type 1 | Type 2 | Type 3 | Type 4 |
| (1) | (2) | (3) | (4) | (5) | (6) |
| i) | Exterior walls: | ||||
| a) Fire separation less than 3.7 m: | |||||
| 1) Bearing | 240 | 120 | 120 | 60 | |
| 2) Non-bearing | 120 | 90 | 60 | 60 | |
| b) Fire separation of 3.7 m or more but less than 9 m: | |||||
| 1) Bearing | 240 | 120 | 120 | 60 | |
| 2) Non-bearing | 90 | 60 | 60 | 60 | |
| c) Fire separation of 9 m or more: | |||||
| 1) Bearing | 240 | 120 | 120 | 60 | |
| 2) Non-bearing | 60 | 60 | 60 | 60 | |
| ii) | Fire separation assemblies (like fire check doors) | 120 | 120 | 120 | 120 |
| iii) | Fire enclosures of exits | 120 | 120 | 120 | 120 |
| iv) | Shafts for services, lift hoistway and refuse chutes | 120 | 120 | 120 | 120 |
| v) | Vertical separation between adjacent tenant spaces | 60 | 60 | 60 | 60 |
| vi) | Dwelling unit separation: | ||||
| a) Load bearing | 120 | 120 | 60 | 60 | |
| b) Non-load bearing | 60 | 60 | 30 | 30 | |
| vii) | Interior bearing walls, bearing partitions, columns, beams, girders, trusses (other than roof trusses) and framing | ||||
| a) Supporting more than one floor | 240 | 120 | 120 | 120 | |
| b) Supporting one floor only | 180 | 90 | 60 | 60 | |
| c) Supporting a roof only | 180 | 90 | 60 | 60 | |
| Sl No. | Structural/Non-Structural Element | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction | Fire Resistance Ratings (min) for Type of Construction |
| Sl No. | Structural/Non-Structural Element | Type 1 | Type 2 | Type 3 | Type 4 |
| (1) | (2) | (3) | (4) | (5) | (6) |
| viii) | Walls supporting structural members | 180 | 90 | 60 | 60 |
| ix) | Floor construction | 120 | 90 | 60 | 60 |
| x) | Roof construction: | ||||
| x) | a) 5 m or less in height to lowest member | 120 | 90 | 60 | 60 |
| x) | b) More than 5 m but less than 6.7 m in height to lowest member | 60 | 60 | 60 | 60 |
| x) | c) 6.7 m or more in height to lowest member | 060* | 060* | 060* | 060* |
| * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. | * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. | * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. | * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. | * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. | * 60 min should be adopted when associated building services/cables are running at higher levels and supported from/near the roof, like in airports. |
Exceptions and deviations to the general provisions of requirements of individual occupancies are given as applicable to each type of occupancy in 6.1 to 6.9. In case of practical difficulty or to avoid unnecessary hardship, without sacrificing reasonable safety, local head, fire services may consider exemptions from this Part.
3.4.1 The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke, or fumes, which may otherwise contribute to the loss of lives and property.
The fire resistance of a building or its structural and non-structural elements is expressed in minutes against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fire. The fire-resistance test for structural element should be done in accordance with accepted standards [F(2)]. For the purpose of this Part, the types of construction according to fire resistance should be classified into four categories, namely, Type 1 Construction, Type 2 Construction, Type 3 Construction and Type 4 Construction. The minimum fire resistance ratings of structural and non-structural members for various types of construction is given in Table 1.
Non-combustible materials should be used for construction of buildings, and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 120 min rating. The walls for the chimney should be of Type 1 or Type 2 Construction depending on whether the flue gas temperature is above 200 °C or less, respectively.
3.4.2 It is required that a structural and/or non-structural element/component to have the requisite fire resistance rating as per Table 1. The fire resistance rating for the structural and non-structural elements are based on guidelines as per approved and accepted standards. The fire rating should be validated and certified with a view to meeting the requirements of Table 1. In the absence of any validated/certified rating, guidance may be obtained from the information available in Annex C.
3.4.3 Load bearing steel beams and columns of buildings having total covered area of 500 m2and above need to be protected against failure/collapse of structure in case of fire. This could be achieved by use of appropriate
methodology using suitable fire resistance rated materials along with suppression system (see Annex C, Table 25, and Table 26).
3.4.4 The false ceiling, including all fixtures used for its suspension, need to be of non-combustible material. To provide adequate fire resistance to the ceiling in order to prevent spread of fire across ceiling.
3.5.3.1 A building or portion of the building may be occupied during construction, repairs, alterations, or additions only if all means of exit and fire protection measures are in place and continuously maintained for the occupied part of the building.
3.5.3.2 A high rise building during construction should be provided with the following fire protection measures, which should be maintained in good working condition at all the times:
a) Dry riser of minimum 100 mm diameter pipe with hydrant outlets on the floors constructed with a fire service inlet to boost the water in the dry riser and maintenance should be in accordance with good practice [F(5)].
b) Drums of 2 000 litre capacity filled with water with two fire buckets on each floor;
c) A water storage tank of minimum 20 000 litre capacity, which may be used for other construction purposes also.