CAR Parking Facilities
G-1 The provisions given in G-2 to G-5 should apply to parking structures of the closed or open type, within buildings above or below grade.
G-2 GENERAL
a) Where both parking and repair operations are conducted in the same building, the entire building should comply with the requirements for Group G occupancies, unless the parking and repair sections are effectively separated by separation walls of 120 min fire rating.
b) Floor surfaces should be non-combustible, sloping towards drains to remove accumulation of water.
c) Those parts of parking structures located within, immediately above or below, attached to, or less than
3 m away from a building used for any other purpose should be separated by fire resistant walls and floors having fire resistance rating of not less than 120 min. This should exclude those incidental spaces which are occupied by cashier, attendant booth or those spaces used for toilets, with a total area not exceeding 200 m2.
d) Vehicle ramps should not be considered as exits unless pedestrian facilities are provided.
e) Other occupancies like fuel dispensing, should not be allowed in the building. Car repair facilities, if provided, should be separated by 120 min fire resistant construction.
f) In addition to fire protection requirements as per Table 7A to Table 7J, appropriate fire detection and suppressions systems should be provided for the protection of hydraulic oil tank and pumps located below ground level for operation of car lifts.
g) Means of egress should meet the requirements specified in 4
G-3 Open Parking Structures (including Multi-level Parking and Stilt Parking)
a) The term open parking structure specifies the degree to which the structure's exterior walls must have openings. Parking structures that meet the definition of the term open parking structure provide sufficient area in exterior walls to vent the products of combustion to a greater degree than an enclosed parking structure.
b) A parking structure having each parking level wall openings open to the atmosphere, for an area of not less than 0.4 m² for each linear metre of its exterior perimeter should be construed as open parking structure. Such openings should be distributed over 40 percent of the building perimeter or uniformly over two opposing sides. Interior wall lines should be at least 20 percent open, with openings distributed to provide ventilation, else, the structure should be deemed as enclosed parking structures.
NOTE — A car park located at the stilt level of a building (not open to sky) can be considered an open or an unenclosed car park if any part of the car park is within 30 m of a permanent natural ventilation opening and any one of the following is complied with towards the permanent natural ventilation requirement:
-
50 percent of the car park perimeter should be open to permanent natural ventilation.
-
At least 75 percent of the car park perimeter is having the 50 percent natural ventilation opening.
c) All stilt parking is required to be provided with sprinkler system where such buildings are required to be sprinklered.
d) Open parking structures are not required to be provided with compartmentation.
e) Open car parking (open to sky) within building complex having fire hydrant system should also need to be protected with yard hydrant installation system in accordance with good practice [F(29)].
G-4 Enclosed Parking Structures
a) Those car parking structures which are enclosed on all sides and on top, not falling within the definition of open car parking [see G-3(b)] and also those situated in the basements should be known as enclosed car parking structures.
b) All sprinklers in car parking should be standard response type with minimum K-factor of 80, area coverage of 9 m² and designed as per good practice [F(20)].
c) For smoke ventilation requirement of car parking, see 4.6
d) All fire exit doors from the car parking to exits should be painted green and should display exit signage.
G-5 Automated CAR Parking Utilizing Mechanical or Computerized/ Robotic Means
a) Automated car parking structure can be of open parking type or enclosed types.
b) Automated car parking facilities pose more hazard compared to manual parking due to following reasons:
-
High density of cars due to close stacking one over another.
-
Lack of provision on fire separation/compartmentation horizontal or vertical leading to rapid fire spread.
-
Non-availability of any person to notice/control the fire in initial stages.
-
Limited access to firefighting personnel.
-
Extensive height and depth involved with highly combustible load.
c) All basements should deploy sprinkler system with not less than K 115 quick response sprinklers, with a minimum of 2 sprinkler for each vehicle with not more than 7.2 m2coverage per sprinkler. The area of operation for basement sprinkler should not be less than 230 m2. This should be applicable to both internal combustion engines (ICE) and electric battery operated or hybrid vehicles. All the sprinklers installed should be protected with a sprinkler guard.
d) All basements that deploy stack parking with one car above the other, where 2 sprinklers cannot be installed for the car below, a quick response extended coverage horizontal side wall of K 115 should be deployed. The pressure rating for this sprinkler should be based on original equipment manufacturers (OEM) recommendation based on the length and width covered. This sprinkler coverage should be within the OEM listing and approvals. Electric or hybrid car should not be parked on stack parking at any level. All the sprinklers installed should be protected with a sprinkler guard.
e) All buildings with automated puzzle parking without human interface should deploy sprinklers as applicable for normal parking. However, the riser should be limited to 24 m height, and additional risers with isolation valves should be added for each riser of 15 m thereon. This is to facilitate maintenance and isolation in case of false activation of sprinklers. All the sprinklers installed should be protected with a sprinkler guard.
f) Fire escape staircases, at least 1 250 mm wide should be provided at appropriate locations so that no place is more than 45 m from the nearest staircase. Horizontal walkways, at least 1 000 mm wide for access to all the areas should be provided at every parking level.
g) Travel distance and means of egress should be governed by the respective sections of this NBCS.
h) The hazardous areas like DG sets, transformers, HT/LT panels for the parking lot should be suitably segregated from other areas as per requirements given in this NBCS and all such areas should be protected by suitable automatic fire suppressions systems.
G-6 Requirements for Electric Vehicles (EV) CAR Parking
See also 10.7 of Part D ‘Building Services, Section 2 Electrical and Allied Installation’ of this NBCS, including regarding electrical safety and location.
EV car parking are best planned in outdoors in well ventilated condition or in separate parking building at/above ground level having naturally cross-ventilated sides. Wherever EVs are designated in the regular car parking they should be segregated from other vehicles using both passive means and active measures of fire protection. The preferred locations are in the ground level and in no case below the first basement. Charging points for EVs may not be permitted below the ground level; and when permitted the same should be restricted to first basement. To enable immediate attention, the EV charging points for the EVs should be available at the entrance/first opportunity of the basement. Isolation cut-off switches (and fireman’s emergency switch) should preferably be of the automated type or when manually operated should be located at the ground level also.
Active protection measure includes one or more of: water mist sprinkler system, and smart detection/monitoring system that enables early detection of thermal runaway issues that can flare up the fire should it happen. Fire suppressing materials using vermiculite/clay/mica based encapsulating agents that provide satisfactory performance may also be used.
The passive protection measures include fire rated walls (preferred over fire curtains/smoke curtains), fire doors, etc and additional protection measures to protect the structural elements from possible rising heat due to fire/hot gases. In the case of basements, maximum sizes of such a compartment for the EV parking (and charging) stations should be 1 000 m2.
NOTE — The above provisions may be modified based on the availability of more suitable/better extinguishing media that proves effective against such fires.