a) The minimum steady-state velocity of the ventilation airflow moving toward the fire within an enclosed trainway or enclosed passageway that is required to control back layering at the fire site, such that a tenable environment is maintained along the path of egress upstream of the fire, and as required for designated points of safety.
b) The equation for critical velocity is as follows:
where
𝑉𝑐 = critical velocity (m/s or fpm)
𝐴 = the annulus area (not including the area of blockages, such as vehicles) perpendicular to the flow (m2 or ft2)
C p = the specific heat of the air (kJ/kg/K or Btu/lb/R)
g = acceleration due to gravity (m/s2 or ft/s2)
G = absolute value of tunnel grade, as a percent
K g = grade factor
H = height from the base of the fire to the tunnel ceiling at the fire site (not tunnel height) (m or ft)
K 1 = Critical Froude number factor with a constant value of 0.606 (critical Froude number of the negative one-third power)
ρ = average density of the approach (upstream) air (kg/m3 or lb/ft3)
Q = convective heat the fire adds directly to the air at the fire site (kW or Btu/s)
T = temperature of the approach air (K or R)
T f = Average temperature of the fire site gases (K or R)