Horizontal exits should be permitted for up to 100 percent of the number of horizontal exits and required egress capacity, provided that not more than 50 percent of the number and required capacity is into a single building and provided they comply with the following provisions:
a) Width of the horizontal exit should at least be the same as that of the exit doorways.
b) A horizontal exit should be equipped with at least one fire/smoke door of a minimum 60 min fire resistance, of self-closing type. Further, it should have direct connectivity to the egress staircase for evacuation.
c) Where there is a difference in level between connected areas for horizontal exits or ramps, slope not more than 1 in 12 should be provided.
d) Doors in horizontal exits should be able to open at all times from both sides.
H-5.4.10 Platform Screen and Edge Door
Horizontal sliding platform screen or platform edge doors should be permitted to separate the platform from the trainway in stations, provided that the doors permit emergency egress from the train to the platform regardless of the stopping position of the train; and the doors provide egress when a force not exceeding 220 N is applied from the train side of the doors. The doors should be designed to withstand positive and negative pressures caused by passing trains.