| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| i) | Abrasive manufacturing premises | R | R | R | NR | Required for packing material/other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| ii) | Aerated water factories, mineral water factories | R | R | R | NR | Required for packing material/ bottles and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| iii) | Agarbatti manufacturing | R | R | R | NR | Required for packing material/Finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| iv) | Analytical and/or quality control laboratories (without pilot plant) | R | R | R | Required if the combined floor area of the building is more than 5 000 m2 | NR | Suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/Storage blocks | |
| Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| | | | | | | exceeds 5 000 m2 | |
| v) | Areca nut slicing and/or betel nut factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| vi) | Asbestos steam packing and lagging manufac-turers | R | R | R | NR | NR | Suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | |
| vii) | Battery charging/battery service station | R | R | R | R | R | Suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | Water mist systems as per IS 15519 |
| Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| viii) | Battery manufacturing | R | R | R | R | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | Water mist systems in battery charging stations as per IS 15519 |
| ix) | Breweries | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| x) | Brick works | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xi) | Canning factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xii) | Cardamom factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xiii) | Cement factories and/or asbestos or concrete products manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | Clean agent-inert gas systems (CO2, Nitrogen) for bag filters, mill house, coal bins |
| xiv) | Ceramic factories and crockery and stoneware pipe manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xv) | Clay works | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xvi) | Clock and watch manufacturing | R | R | R | NR | Raw Material godowns should be sprinklered if the value of plastic/rubber and other similar commodities in the storage area exceeds 20 percent of the total | Manual fire alarm system should be provided throughout, operations like spray painting, wood working, solvent cleaning etc, should need to be spot-protected if combined area | |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| | | | | | value of the storage building | occupied by such operations exceed 10 percent of the total manufacturing area | |
| xvii) | Coffee curing, roasting and grinding premises | R | R | R | Required if the area occupied by process building exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | If combined area of the entire factory is more than 2 000 m2, manual fire alarm system should be required, Suitable detection system backed up by Manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | If combined area of process and storage blocks in the same building exceeds 2 000 m2, sprinkler installation will be required in the entire area |
| xviii) | Condensed milk factories, milk pasteurising plant and dairies | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xix) | Confectionery manufacturing | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xx) | Crockery and stoneware pipe manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxi) | Electric generating houses (Hydro electric) | R | R | R | NR | Sprinkler protection for storage areas not forming part of main occupancy if area exceeds 2 000 m2 | Auto fire alarm system for all areas except detached storage buildings and utility blocks where manual alarm systems should be provided | Water spray system for transformers, FDS/NIFPS system, cable galleries, conveyors including transfer towers, etc as per IS 3034 and IS 15325 |
| xxii) | Electric Lamps (Incandescent and Fluorescent) and TV Picture Tube Manufacturing | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxiii) | Electric Sub-Station/Distribution Station | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | Water spray system for transformers if capacity thereof is more than 10 MVA or oil capacity exceeds 2 000 litre. |
| Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² | Appendix '1' to Annex N Low Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m² |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| | | | | | | | (As per CEA Regulations and IS 3034, IS 15325) |
| xxiv) | Electro Plating Works | R | R | R | NR | NR | NR | |
| xxv) | Electronic and/or Computer equipments Assemble and Manufactures | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xxvi) | Engineering workshops heavy (Structural Steel Fabricators, Sheet Metal Fabricators (Tin Printing excluded), Hot or Cold Rolling, Pipe Extruding, Stamping, Pressing, Drawing (other than wire Drawing) or Forging Mills, Ore Crushing Mills, Ferrous and non Ferrous Metal Smelting or Extraction Works and Foundries (allowing storage of Wooden | R | R | R | NR | Raw material godowns should be sprinklered if the value of plastic/rubber and other similar commodities in the storage area exceeds 20 percent of the total value of the storage building. | Manual fire alarm system should be provided throughout, operations like manufacture of plastic/rubber components, powder coating/spray painting, drying of painted goods, use or storage of flammable liquids having flash point of 23 °C and below, wood working, upholstering, engine testing and flammable gas plant should need to be spot-protected by appropriate means if combined area | |
| Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| Patterns only) and galvanizing works and the like) | | | | | | occupied by such operations exceed 10 percent of the total manufacturing area. Else such areas should be fire separated from the main operations | |
| xxvii) | Engineering workshops Light (Blacksmiths, Electroplating, Anodizing or Lead, Zinc or other Metal Coating Works, Machine Shops, Heat Treatment shops, Electro Magnets manufacturing, Electrical and Mechanical Machinery Assemblers/Manufacturers, General Engineering Goods and Merchandise Manufacturers, Maintenance and Repair Workshops, Mfrs. of Welding Electrodes and Wire drawing, Automobile factories and the like) | | | | | | occupied by such operations exceed 10 percent of the total manufacturing area. Else such areas should be fire separated from the main operations | |
| Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xxviii) | Fruits and vegetables dehydrating/drying factories | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxix) | Fruit products and condiment factories | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxx) | Glass and glass Fibre manufacturing | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxi) | Gold thread factories/ gilding factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxii) | Granite manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | If inflammable liquids having a flash point of less than 65° are used, manual foam spray |
| Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix ‘1’ to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| | | | | | | | system should be used in the areas concerned |
| xxxiii) | Gum and/or Glue and Gelatine Manufacturing | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxiv) | Ice Candy and Ice-cream Manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxv) | Ice Factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxvi) | Ink (excluding Printing Ink) Factories | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xxxvii) | Laundries | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxviii) | Mica products manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxix) | Pottery works | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xl) | Poultry farms | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xli) | Salt Crushing Factories and Refineries | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xlii) | Sugar Candy Manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xliii) | Sugar Factories and Refineries | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xliv) | Tanneries/Leather Goods Manufacturers | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xlv) | Tea Blending and Tea Packing Factories | R | R | R | Required if the area occupied by process building exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | If combined area of the entire factory is more than 2 000 m2, manual fire alarm system should be required, suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | If combined area of process and storage blocks in the same building exceeds 2 000 m2, sprinkler installation will be required in the entire area |
| Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 | Appendix '1' to Annex NLow Hazard Factories/Industries with Aggregate Built-up area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xlvi) | Umbrella Assembling Factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xlvii) | Vermicelli Factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xlviii) | Water Treatment/Water Filtration Plants and Water Pump House | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xlix) | Zinc/Copper/Aluminium Factories | R | R | R | NR | NR | Suitable detection system backed up by manual call stations should be provided for the entire factory where combined area of the process/storage blocks exceeds 5 000 m2 | |
| R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. | R – Required. NR – Not Required. |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| i) | Airport and other transportation terminal building | R | R | R | To be fully sprinklered | To be fully sprinklered (cargo) | To be fully protected by automatic intelligent fire alarm system | Kitchen hoods and ducts should be protected with wet chemical systems as per this NBCS. Also, systems as per ICAO standards. |
| ii) | Aluminium factories | R | R | R | NR | NR | NR | |
| iii) | Bakeries | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| iv) | Beedi factories | R | R | R | NR | NR | NR | |
| v) | Biscuit factories | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| vi) | Bobbin factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| vii) | Bookbinders, envelopes and paper bag manufacturers | R | R | R | Required when a single un-compartmented area is more than 2 000 m² | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| viii) | Cable manufacturing | R | R | R | Required when a single un-compartmented area is more than 2 000 m² | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| ix) | Carbon paper/typewriter ribbon manufacturers | R | R | R | Required when a single un-compartmented area is more than 2 000 m² | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| x) | Cardboard box manufacturing | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xi) | Carpenters, wood wool and furniture manufacturers. Basket weavers, cane furniture manufacturing | R | R | R | Required when a single un-compartmented area is more than 2 000 m² | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xii) | Carpet and drugget factories | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xiii) | Chemical manufacturing involving chemicals, dyes, intermediates, pigments, acids, medicinal/ pharmaceuticals formulation and toilet preparation including soap manufacturing, chemical mixing and blending factories using no chemicals/solvents having flash point below 23 °C | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | If the quantity of chemicals/ solvents having flash point below 23 °C is less than 200 litre in process and there is no storage of such solvents/chemicals more than 200 litre then such industries can be considered under this table. Else, see High hazard |
| xiv) | Cigar and cigarette factories | R | R | R | Required in full | Required in full | Automatic fire alarm system should be provided for godown buildings, manual system for process blocks | |
| Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² | Appendix '2' to Annex N Ordinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m² |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xv) | Coffee grinding premises | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xvi) | Coir, carpets, rugs and tobacco, hides and skin presses | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m² in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xvii) | Cork products manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xviii) | Dry cleaning, dyeing, laundries | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m² | |
| xix) | Electric generating stations (other than hydel) | R | R | R | NR | Sprinkler protection for storage areas not forming part of main occupancy if area exceeds 2 000 m² | Automatic fire alarm system for all areas except detached storage buildings and utility blocks where manual alarm systems should be provided | Water spray system for transformers, FDS/NIFPS system, cable galleries, conveyors including transfer towers, etc as per IS 3034 and IS 15325 |
| Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix ‘2’ to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xx) | Enamelware factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxi) | Filter and wax paper manufacturing | R | R | R | Required when a single un-compartmented area is more than 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxii) | Flour mills | R | R | R | Required if combined floor plate area exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxiii) | Garment makers | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxiv) | Ghee factories (other than vegetable) | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xxv) | Grain and/or seeds disintegrating and/or crushing factories | R | R | R | Required if combined floor plate area exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxvi) | Grease manufacturing | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxvii) | Hat and topee factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxviii) | Hosiery, lace, embroidery and thread factories | R | R | R | Required if combined floor plate area exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxix) | Incandescent gas mantle manufacturers | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| SI No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| xxx) | Industrial gas manufacturing Including halogenated hydrocarbon gases | R | R | R | NR | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2000 m2 | |
| xxxi) | Linoleum factories | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxii) | Man-made yarn/fibre manufacturing (except acrylic) | R | R | R | Required if combined floor plate area exceeds 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Automatic fire alarm system should be provided when combined floor plate exceeds 5 000 m2, else manual systems should be provided | |
| xxxiii) | Manure and fertiliser works. (blending, mixing and granulating only) | R | R | R | NR | NR | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxiv) | Mineral oil blending and processing | R | R | R | Required when a single un-compartmented area is more than 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding | Manual fire alarm system for entire unit if area of single largest building | |
| Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 | Appendix '2' to Annex NOrdinary Hazard Factories/Industries with Aggregate Built-up Area more than 2 500 m2 |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Sprinkler System | Sprinkler System | Fire Alarm System | Special Protection |
| Sl No. | Description | Extinguisher | Hose Reel | Hydrant System | Process Blocks | Storage Blocks | Fire Alarm System | Special Protection |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| | | | | | 2 000 m2 in area | exceeds 2 000 m2 | |
| xxxv) | Oil and leather cloth factories | R | R | R | Required when a single un-compartmented area is more than 2 000 m2 | Required for Packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxvi) | Oxygen plants | R | R | R | Required for manufacturing blocks | Required for storage blocks | Automatic fire alarm system should be provided throughout | |
| xxxvii) | Plywood manufacturing/wood veneering factories | R | R | R | Required when a single un-compartmented area is more than 2 000 m2 | Required for packing material/finished goods and other raw materials godowns if exceeding 2 000 m2 in area | Manual fire alarm system for entire unit if area of single largest building exceeds 2 000 m2 | |
| xxxviii) | Paper and cardboard mills | R | R | R | NR | Raw material and Finished goods storage should be provided with sprinklers | Automatic fire alarm system should be provided throughout | |
| xxxix) | Plastic goods manufacturing polytetra fluoroethylene, flourinated ethylene- | R | R | R | Required if combined floor plate area exceeds 2 000 m2 | Raw material and finished goods storage should be provided with sprinklers if area exceeds | Manual fire alarm system for entire unit if area of single largest building | |